 Optyma™ control AK-RC 111 single phase

© Danfoss | DCS (vt) | 2020.03

BC309238530328en-000101 | 11

In1

INP-1 input setting

 8 = Night mode digital input 

(energy saving, N.O.)

 7 = Stop defrosting remotely (N.O.) 

(reads rising edge of impulse) 

 6 = Start defrosting remotely (N.O.) 

(reads rising edge of impulse) 

 5 = Stand-by remotely (N.O.) (In 

order to indicate Stand-By 

mode, the display shows ‘In5’ 

alternating with the current 

view) 

 4 = Pump-down pressure switch 

(N.O.)

 3 = Man-in-room alarm (N.O.)

 2 = Compressor protection (N.O.)

 1 = Door switch (N.O.)

 0 = disabled

-1 = Door switch (N.C.)

-2 = Compressor protection (N.C.)

-3 = Man-in-room alarm (N.C.)

-4 = Pump-down pressure switch 

(N.C.)

-5 = Stand-by remotely (N.C.) (In 

order to indicate Stand-By 

mode, the display shows ‘In5’ 

alternating with the current 

view) 

-6 = Start defrosting remotely (N.C.) 

(reads falling edge of impulse)

-7 = Stop defrosting remotely (N.C.) 

(reads falling edge of impulse)

-8 = Night mode digital input 

(energy saving, N.C.)

2

In2

INP-2 input setting

(like In1)

1

bEE

Buzzer enable

0 = disabled

1 = enabled

1

mOd

Thermostat functioning mode

0 = Cold function

1 = Hot function

(in this mode defrosting and fan 

disable Fst are excluded)

0

P1

Password type of protection

(active when PA is not equal 0)

0 = only display set point

1 = display set point, AUX,  

light access

2 = access in programming  

not permitted

3 = access in second level 

programming not permitted

3

PA

Password

(see P1 for the type of protection)

0...999

0 = not active

0

reL

Release software

indicates software version

2

(read only)

4.11  Switching on the AK-RC 

111 electronic controller

4.12  Cold/hot activation/

deactivation conditions

4.13  Manual defrosting 

activation/deactivation

After wiring the electronic controller correctly, power up at 230 V AC; the display panel will 

immediately emit a beep and all the LEDs will come on simultaneously for a few seconds.

In cold mode (mOd=0)

, the 

AK-RC 111

 controller activates the compressor when cold room 

temperature exceeds s differential (r0); it deactivates the compressor when cold room 

temperature is lower than the setting.
If Pump-Down function is selected (parameter AU1/AU2 = 4/-4), see chapter 4.16 for compressor 

activation/deactivation conditions.

In hot mode (mOd=1)

, the 

AK-RC 111

 controller activates the heat output (COMPR output) when cold 

room temperature drops below setting-differential (r0); it deactivates the heat output (COMPR output) 

when cold room temperature is higher than the setting.

To defrost just press the dedicated key (see section 5.2) to activate the elements relay. Defrosting will 

not take place if the end-of-defrost temperature setting (d2) is lower than the temperature detected 

by the evaporator sensor. Defrosting ends when the end-of-defrost temperature (d2) or maximum 

defrost time (d3) is reached, or due to forced manual defrost termination (end of defrost button or 

digital input).

Содержание AK-RC 111

Страница 1: ...User Guide Optyma control AK RC 111 single phase...

Страница 2: ...ing and displaying the set points 8 4 7 Level 1 programming user level 8 4 8 List of Level 1 variables user level 8 4 9 Level 2 programming installer level 9 4 10 List of Level 2 variables installer l...

Страница 3: ...iliary relays with parameter configured Integrated RS 485 Modbus connection for Danfoss System Manager or standard Modbus RTU network Emergency operation in the event of a faulty probe environment Sma...

Страница 4: ...n the electronics For the purposes of assembly and use the electronic AK RC 111 control unit comes with 3 seals to be fitted between the fixing screws and the box back panel 1 user s manual Fig 1 Rais...

Страница 5: ...e panel and carry out thorough reading programming of all the parameters Note Make all the electrical connections as illustrated in the diagram for the corresponding model see relative table in append...

Страница 6: ...nstalled relay Card output characterstics Note Compressor Relay 30A AC1 10 A 250 V AC3 2HP 100000 cicli The sum of contemporary absorptions of these outputs has not to exceed 16 A Defrost Relay 30A AC...

Страница 7: ...Cold room temperature parameters 7 Up Mute buzzer alarm 2 Stand by flashes on stand by outputs are deactivated 8 Room light flashes if door switch activated 9 Cold indicates activation of compressor 1...

Страница 8: ...T key together with the or key When configuration values have been set you can exit the menu by pressing the or keys simultaneously for a few seconds until the cold room temperature reappears 5 The ne...

Страница 9: ...d working for the F6 time If activation time coincides with the defrosting time end of defrosting is awaited 0 240 min 0 function not activated 0 min F7 Evaporator fans duration for air recirculation...

Страница 10: ...he temperature value read by the evaporator sensor is higher than this value 45 99 C 99 C Fd Fst differential 1 10 C 2 C LSE Minimum value attributable to setpoint 45 HSE 1 C 45 C HSE Maximum value at...

Страница 11: ...econd level programming not permitted 3 PA Password see P1 for the type of protection 0 999 0 not active 0 reL Release software indicates software version 2 read only 4 11 Switching on the AK RC 111 e...

Страница 12: ...must allow opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve For capillary systems without thermostat valve it is only necessary to control the cycle inversion so...

Страница 13: ...room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm one where applicable are deactivated...

Страница 14: ...front opening hinge 5 Box closure screws 6 Board fixing screws 7 Magneto thermal cut out power breaker 8 CPU board 9 Polycarbonate screw cover 10 Terminal for earth connections N F d d 1 2 3 4 5 6 7...

Страница 15: ...User Guide Optyma control AK RC 111 single phase Danfoss DCS vt 2020 03 BC309238530328en 000101 15 8 0 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3220...

Страница 16: ...oss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady...