manualshive.com logo in svg
background image

User Guide 

|

 Optyma™ control AK-RC 111 single phase

© Danfoss | DCS (vt) | 2020.03

BC309238530328en-000101 | 13

6.0 Troubleshooting

In the event of any anomalies of the

 AK-RC 111

, it notifies the operator by means of the alarm codes 

displayed on the display and an audible signal emitted by a buzzer inside the control panel. The EL 

and EH temperature alarms remain visible even after their return (alarm icon lights on) until their 

acknowledgment (by pressing the key). If an alarm condition occurs, one of the following messages 

will be displayed on the display:

Alarm code

Possible cause

Solution

E0

Cold room temperature sensor not working properly

•  Check that cold room temperature 

sensor is working properly

•  If the problem persists, replace the 

sensor

E1

Defrost sensor not working properly

(In this case defrosts will last time d3)

•  Check that defrost sensor is 

working properly

•  If the problems persists, replace the 

sensor

E2

Eeprom alarm

An EEPROM memory alarm has been detected

(All outputs except the alarm one are deactivated)

•  Switch unit off and back on 

E8

Man in cold room alarm

•  Reset the alarm input inside the 

cold room

Ec

Compressor protection tripped

(e.g. thermal protection or max pressure switch)

(All outputs except the alarm one – where applicable – 

are deactivated)

•  Check that compressor is working 

properly

•  Check compressor absorption
•  If the problem persists, contact the 

technical assistance service

Ed

Open door Alarm

.

When the door is opened and after tdo time, it’s setted 

back the normal functioning giving door open alarm 

(Ed).

•  Check door switch status 
•  Check door switch connections
•  If the problem persists contact the 

technical assistance service

E9

Cell light alarm.

The light of the cell has been on for a time greater than 

tdo.

•  Turn off the light

EH

Maximum temperature alarm.

The temperature inside the cold room has exceeded 

the max. temperature alarm setting (see variables A2, 

user programming level

)

•  Check that the compressor is 

working properly.

•  Sensor not reading temperature 

properly or compressor start/stop 
control not working.

EL

Minimum temperature alarm.

The temperature inside the cold room has exceeded 

the min. temperature alarm setting (see variables A1, 

user programming level

).

•  Check that the compressor is 

working properly.

•  Sensor not reading temperature 

properly or compressor start/stop 
control not working.

Содержание AK-RC 111

Страница 1: ...User Guide Optyma control AK RC 111 single phase...

Страница 2: ...ing and displaying the set points 8 4 7 Level 1 programming user level 8 4 8 List of Level 1 variables user level 8 4 9 Level 2 programming installer level 9 4 10 List of Level 2 variables installer l...

Страница 3: ...iliary relays with parameter configured Integrated RS 485 Modbus connection for Danfoss System Manager or standard Modbus RTU network Emergency operation in the event of a faulty probe environment Sma...

Страница 4: ...n the electronics For the purposes of assembly and use the electronic AK RC 111 control unit comes with 3 seals to be fitted between the fixing screws and the box back panel 1 user s manual Fig 1 Rais...

Страница 5: ...e panel and carry out thorough reading programming of all the parameters Note Make all the electrical connections as illustrated in the diagram for the corresponding model see relative table in append...

Страница 6: ...nstalled relay Card output characterstics Note Compressor Relay 30A AC1 10 A 250 V AC3 2HP 100000 cicli The sum of contemporary absorptions of these outputs has not to exceed 16 A Defrost Relay 30A AC...

Страница 7: ...Cold room temperature parameters 7 Up Mute buzzer alarm 2 Stand by flashes on stand by outputs are deactivated 8 Room light flashes if door switch activated 9 Cold indicates activation of compressor 1...

Страница 8: ...T key together with the or key When configuration values have been set you can exit the menu by pressing the or keys simultaneously for a few seconds until the cold room temperature reappears 5 The ne...

Страница 9: ...d working for the F6 time If activation time coincides with the defrosting time end of defrosting is awaited 0 240 min 0 function not activated 0 min F7 Evaporator fans duration for air recirculation...

Страница 10: ...he temperature value read by the evaporator sensor is higher than this value 45 99 C 99 C Fd Fst differential 1 10 C 2 C LSE Minimum value attributable to setpoint 45 HSE 1 C 45 C HSE Maximum value at...

Страница 11: ...econd level programming not permitted 3 PA Password see P1 for the type of protection 0 999 0 not active 0 reL Release software indicates software version 2 read only 4 11 Switching on the AK RC 111 e...

Страница 12: ...must allow opening of the cycle inversion solenoid valve and closure of the liquid solenoid valve For capillary systems without thermostat valve it is only necessary to control the cycle inversion so...

Страница 13: ...room alarm Reset the alarm input inside the cold room Ec Compressor protection tripped e g thermal protection or max pressure switch All outputs except the alarm one where applicable are deactivated...

Страница 14: ...front opening hinge 5 Box closure screws 6 Board fixing screws 7 Magneto thermal cut out power breaker 8 CPU board 9 Polycarbonate screw cover 10 Terminal for earth connections N F d d 1 2 3 4 5 6 7...

Страница 15: ...User Guide Optyma control AK RC 111 single phase Danfoss DCS vt 2020 03 BC309238530328en 000101 15 8 0 Ordering Type Code no OPTYMATM Control single phase 2 HP including two sensors 080Z3220...

Страница 16: ...oss reserves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady...

Отзывы: