Instructions RI8SE202 © Danfoss 07/2017 

9

Fault message

In an error situation the LED’s on the front will flash and the alarm relay 
will be activated. If you push the top button in this situation you can see 
the alarm report in the display.
There are two kinds of error reports - it can either be an alarm occurring 
during the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired. 
E-alarms, on the other hand, will become visible the moment the error 
occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:

Code / Alarm text via 
data communication

Description

Alarm 
relay 
groups 
(P41)

A1/---  High t.alarm

High temperature alarm

1

A2/---  Low t. alarm

Low temperature alarm

2

A4/--- Door alarm

Door alarm

8

A5/--- Max hold time

The ”o16” function is activated 
during a coordinated defrost

16

A13/--- High temp S6

Temperature alarm. High S6

1

A14/--- Low temp S6

Temperature alarm. Low S6

2

A15/--- DI1 alarm

DI1 alarm

8

A16/--- DI2 alarm

DI2 alarm

8

A45/--- Standby mode

Standby position (stopped 
refrigeration via r12 or DI input)

-

A59/--- Case clean

Case cleaning. Signal from DI 
input

-

A97/--- Comp. Safety

Compressor safety. Signal from 
DI3 input

8

AA3/---High brine temp.

High brine temperature alarm

8

E1/---  Ctrl. error

Faults in the controller

32

E6/--- RTC error

Check clock

32

E25/--- S3 error

Error on S3 sensor

4

E26/--- S4 error

Error on S4 sensor

4

E27/--- S5 error

Error on S5 sensor

4

E28/--- S6 error

Error on S6 sensor

4

E50/--- S7 error

Error on S7 sensor

4

---/--- Max Def.Time

Defrost stopped based on 
time instead of, as wanted, on 
temperature

16

Data communication
The importance of individual alarms can be defined with a setting. The 
setting must be carried out in the group "Alarm destinations"

Settings from 
System manager AK-SM

Settings from 
AKM (AKM destination)

Send via
Network

High

1

X

Middle

2

X

Low

3

X

Log only

Disabled

Operating status

(Measure-
ment)

The controller goes through some regulating situ-
ations where it is just waiting for the next point 
of the regulation. To make these “why is nothing 
happening” situations visible, you can see an op-
erating status on the display. Push briefly (1s) the 
upper button. If there is a status code, it will be 
shown on the display. The individual status codes 
have the following meanings:

Ctrl. state:
(Shown in 
all menu 
displays)

Normal regulation

S0

0

Waiting for end of the coordinated defrost

S1

1

When the compressor is operating it must run for 
at least x minutes.

S2

2

When the compressor is stopped, it must remain 
stopped for at least x minutes.

S3

3

The evaporator drips off and waits for the time to 
run out

S4

4

Refrigeration stopped by main switch. Either with 
r12 or a DI-input

S10

10

Refrigeration stopped by thermostat

S11

11

Defrost sequence. Defrost in progress

S14

14

Defrost sequence. Fan delay — water attaches to 
the evaporator

S15

15

Refrigeration stopped due to open ON input or 
stopped regulation

S16

16

Door is open. DI input is open

S17

17

Melt function in progress. Refrigeration is inter-
rupted

S18

18

Modulating thermostat control

S19

19

Emergency cooling due to sensor error *)

S20

20

Manual control of outputs

S25

25

Case cleaning

S29

29

Delay on outputs during start-up

S32

32

Case shut down

S45

45

Other displays:

The defrost temperature cannot be displayed. 
There is stop based on time

non

Defrost in progress / First cooling after defrost

-d-

Password required.  Set password 

PS

Regulation is stopped via main switch

OFF

*) Emergency cooling will take effect when there is lack of signal from a 

defined S3 or S4 sensor. The regulation will continue with a registered 
average cutin frequency. There are two registered values – one for day 
operation and one for night operation.

AD

AP

-K

OOL®

Содержание AK-CC 460

Страница 1: ...Principle Dimensions Instructions AK CC 460 RI8SE202 07 2017 Identification 084B8016 1...

Страница 2: ...her RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal 58 B Alternatively the terminals c...

Страница 3: ...ectly See separate literature No RC8AC Electric noise Cables for sensors DI inputs and data communication must be kept separate from other electric cables Use separate cable trays Keep a distance betw...

Страница 4: ...ion 6 20 AK SM Data communication Display EKA 163 164 L 15 m L 15 m Important All connections to the data communication MODBUS RS 485 and DANBUSS must comply with the requirements for data communicati...

Страница 5: ...arameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to set the value Cutout alarm relay receipt alarm see alarm code A short press of t...

Страница 6: ...Delay for temperature alarm after defrost A12 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 50 C 50 C 30 High alarm limit for thermostat...

Страница 7: ...d changeover activate r21 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal 12 night cover 15 appliance shutdown o02 1 0 15 0 Network address 0 off o03 1 0 240 0 On...

Страница 8: ...1 Temperature measured with S3 sensor u12 1 Status on night operation on or off 1 on u13 1 Temperature measured with S4 sensor u16 1 Thermostat temperature u17 1 Run time of thermostat cooling time in...

Страница 9: ...nations Settings from System manager AK SM Settings from AKM AKM destination Send via Network High 1 X Middle 2 X Low 3 X Log only Disabled Operating status Measure ment The controller goes through so...

Отзывы: