AK-CC
460
Instructions RI8SE202 © Danfoss 07/2017
7
Drip off time
d06
1
0 min.
60 min.
0
Delay for fan start after defrost
d07
1
0 min.
60 min.
0
Fan start temperature
d08
1
-50 °C
0 °C
-5
Fan cutin during defrost
0: stopped
1 & 2: Running
d09
1
0
2
1
Defrost sensor:
0 =Stop on time, 1=S5, 2=S4, 3=S5 and S6
d10
1
0
3
0
Pump down delay
d16
1
0 min.
60 min.
0
Max. aggregate refrigeration time between two defrosts
d18
1
0 hrs
48 hrs
0/OFF
Rail heat during defrost
0: off
1: on
2: Pulsing
d27
1
0
2
2
Max. duration of -d- in display
d40
1
5 min.
240 min.
30 min.
Fan
Fan stop temperature (S5)
F04
1
-50°C
50°C
50
Pulse operation on fans: 0=No pulse operation, 1=At thermostat cuts out only, 2=
Only at thermostat cut outs during night operation
F05
1
0
2
0
Period time for fan pulsation (on-time + off-time)
F06
1
1 min.
30 min.
5
On-time in % of period time
F07
1
0 %
100 %
100
Real time clock
Six start times for defrost.
Setting of hours.
0=OFF
t01 -
t06
1
0 hrs
23 hrs
0
Six start times for defrost.
Setting of minutes.
0=OFF
t11 -
t16
1
0 min.
59 min.
0
Clock - Setting of hours
t07
1
0 hrs
23 hrs
0
Clock - Setting of minute
t08
1
0 min.
59 min.
0
Clock - Setting of date
t45
1
1 day
31 day
1
Clock - Setting of month
t46
1
1 mon.
12 mon.
1
Clock - Setting of year
t47
1
0 year
99 year
0
Miscellaneous
Delay of output signals after start-up
o01
1
0 sec
600 sec
5
Input signal on DI1. Function:
0=not used. 1=status on DI1. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext.main switch. 6=night operation
7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse signal). 12=night cover. 15=appliance
shutdown
o02
1
0
15
0
Network address (0= off)
o03
1
0
240
0
On/Off switch (Service Pin message)
IMPORTANT! o61 must be set prior to o04
(used at LON 485 only)
o04
1
0/Off
1/On
0/Off
Access code 1 (all settings)
o05
1
0
100
0
Software Version
o08
1
Max hold time after coordinated defrost
o16
1
0 min.
360 min.
20
Select signal for display view. S4% (100%=S4, 0%=S3)
o17
1
0 %
100 %
100
Input signal on DI2. Function:
0=not used. 1=status on DI2. 2=door function with alarm when open. 3=door alarm
when open. 4=defrost start (pulse-signal). 5=ext. main switch 6=night operation
7=thermostat band changeover (activate r21). 8=alarm function when closed. 9=alarm
function when open. 10=case cleaning (pulse signal). 12=night cover, 13=coordinated
defrost. 15=appliance shutdown
o37
1
0
15
0
Configuration of light function
: 1=Light follows day /night operation, 2=Light
control via data communication via ‘o39’, 3=Light control with a DI-input, 4=As "2",
but light switch on and night cover will open if the network cut out for more than
15 minutes.
o38
1
1
4
1
Activation of light relay (only if o38=2)
On=light
o39
1
0/Off
1/On
0/Off
Rail heat On time during day operations
o41
1
0 %
100 %
100
Rail heat On time during night operations
o42
1
0 %
100 %
100
Rail heat period time (On time + Off time)
o43
1
6 min.
60 min.
10
Case cleaning. 0=no case cleaning. 1=Fans only. 2=All output Off.
***
o46
1
0
2
0
Selection of EL diagram. See overview page 1
*
o61
1
1
1
1
Access code 2 (partial access)
***
o64
1
0
100
0
Replace the controllers factory settings with the present settings
o67
1
0/Off
1/On
0/Off
Continued
code
1
Min.
Max.
Fac.