Danfoss AK-CC 460 Скачать руководство пользователя страница 6

Instructions RI8SE202 © Danfoss 07/2017 

 

 AK-CC 

460

Menu survey

SW = 1.0x

Parameter

EL-diagram 

page 1 

Min.-

value

Max.-value

Factory 

setting

Actual 

setting

Function

Code

 1

Normal operation
Temperature (setpoint)       

- - -

1

-50°C

50°C

2

Thermostat
Differential

r01

1

0.1 K

20 K

2

Max. limitation of setpoint setting

r02 

1

-49°C

50°C

50

Min. limitation of setpoint setting

r03 

1

-50°C

49°C

-50

Adjustment of temperature indication

r04

1

-10

10

0

Temperature unit (°C/°F)

r05 

1

0/°C

1/F

0/°C

Correction of the signal from S4

r09 

1

-10 K

10 K

0

Correction of the signal from S3

r10 

1

-10 K

10 K

0

Manual service, stop regulation, start regulation (-1, 0, 1)

r12 

1

-1

1

0

Displacement of reference during night operation

r13

1

-50 K

50 K

0

Thermostat function (Read out)
ON/OFF

r14

1

=On/Off

Definition and weighting, if applicable, of thermostat sensors - S4% (100%=S4,  0%=S3)

r15

1

0 %

100 %

100

Time between melt periods

r16 

1

0 hrs

10 hrs

1

Duration of melt periods

r17

1

0 min.

30 min.

5

Temperature setting for thermostat band 2 

. As differential r01 is used

r21

1

-50°C

50°C

2

Correction of the signal from 

S6

r59

1

-10 K

10 K

0

Definition and weighting, if applicable, of thermostat sensors  when night cover is on.  
(100%=S4,  0%=S3)

r61

1

0 %

100 %

100

S4 min. limit, Frost protection. Cooling is stopped.

r98

1

-50°C

20°C

-50°C

Alarms

Delay for temperature alarm

A03

1

0 min.

240 min.

30

Delay for door alarm

A04

1

0 min.

240 min.

60

Delay for temperature alarm after defrost

A12

1

0 min.

240 min.

90

High alarm limit for thermostat 1

A13

1

-50°C

50°C

8

Low alarm limit for thermostat 1

A14 

1

-50°C

50°C

-30

High alarm limit for thermostat 2

A20

1

-50°C

50°C

8

Low alarm limit for thermostat 2

A21

1

-50°C

50°C

-30

High alarm limit for sensor S6 at thermostat 1

A22

1

-50°C

50°C

8

Low alarm limit for sensor S6 at thermostat 1

A23

1

-50°C

50°C

-30

High alarm limit for sensor S6 at thermostat 2

A24

1

-50°C

50°C

8

Low alarm limit for sensor S6 at thermostat 2

A25

1

-50°C

50°C

-30

S6 alarm time delay
With setting = 240 the S6 alarm will be omitted

A26

1

0 min.

240 min.

240

Alarm time delay or signal on the DI1 input

A27

1

0 min.

240 min.

30

Alarm time delay or signal on the DI2 input

A28

1

0 min.

240 min.

30

Signal for alarm thermostat. S4% (100%=S4, 0%=S3)

A36

1

0 %

100 %

100

Delay for S6 (product sensor alarm) after defrost

A52

1

0 min.

240 min.

90

Alarm limit for max. S7 brine temperature

A76

1

-50°C

50°C

8°C

Differential for S7 brine alarm 

A77

1

0.1 K

10 K

3.0 K

Compressor
Min. ON-time

c01

1

0 min.

30 min.

0

Min. OFF-time

c02

1

0 min.

30 min.

0

Time delay for cutin of comp.2

c05

1

0 sec

999 sec

5

Compressor 1 on time when sensor fault (compressor 2 = off)

c86

1

0 min

240 min

15

Compressor 1 off time when sensor fault

c87

1

0 min

240 min

15

Defrost

Defrost method

: 0=none, 1= EL

d01

1

0/No

1/EL

1/EL

Defrost stop temperature

d02

1

0°C

50°C

6

Interval between defrost starts

d03

1

0 hrs/Off 240 hrs

8

Max. defrost duration

d04

1

0 min.

360 min.

45

Displacement of time on cutin of defrost at start-up

d05

1

0 min.

240 min.

0

Содержание AK-CC 460

Страница 1: ...Principle Dimensions Instructions AK CC 460 RI8SE202 07 2017 Identification 084B8016 1...

Страница 2: ...her RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal 58 B Alternatively the terminals c...

Страница 3: ...ectly See separate literature No RC8AC Electric noise Cables for sensors DI inputs and data communication must be kept separate from other electric cables Use separate cable trays Keep a distance betw...

Страница 4: ...ion 6 20 AK SM Data communication Display EKA 163 164 L 15 m L 15 m Important All connections to the data communication MODBUS RS 485 and DANBUSS must comply with the requirements for data communicati...

Страница 5: ...arameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to set the value Cutout alarm relay receipt alarm see alarm code A short press of t...

Страница 6: ...Delay for temperature alarm after defrost A12 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 50 C 50 C 30 High alarm limit for thermostat...

Страница 7: ...d changeover activate r21 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal 12 night cover 15 appliance shutdown o02 1 0 15 0 Network address 0 off o03 1 0 240 0 On...

Страница 8: ...1 Temperature measured with S3 sensor u12 1 Status on night operation on or off 1 on u13 1 Temperature measured with S4 sensor u16 1 Thermostat temperature u17 1 Run time of thermostat cooling time in...

Страница 9: ...nations Settings from System manager AK SM Settings from AKM AKM destination Send via Network High 1 X Middle 2 X Low 3 X Log only Disabled Operating status Measure ment The controller goes through so...

Отзывы: