6
Instructions RI8SE202 © Danfoss 07/2017
AK-CC
460
Menu survey
SW = 1.0x
Parameter
EL-diagram
page 1
Min.-
value
Max.-value
Factory
setting
Actual
setting
Function
Code
1
Normal operation
Temperature (setpoint)
- - -
1
-50°C
50°C
2
Thermostat
Differential
r01
1
0.1 K
20 K
2
Max. limitation of setpoint setting
r02
1
-49°C
50°C
50
Min. limitation of setpoint setting
r03
1
-50°C
49°C
-50
Adjustment of temperature indication
r04
1
-10
10
0
Temperature unit (°C/°F)
r05
1
0/°C
1/F
0/°C
Correction of the signal from S4
r09
1
-10 K
10 K
0
Correction of the signal from S3
r10
1
-10 K
10 K
0
Manual service, stop regulation, start regulation (-1, 0, 1)
r12
1
-1
1
0
Displacement of reference during night operation
r13
1
-50 K
50 K
0
Thermostat function (Read out)
ON/OFF
r14
1
=On/Off
—
—
—
Definition and weighting, if applicable, of thermostat sensors - S4% (100%=S4, 0%=S3)
r15
1
0 %
100 %
100
Time between melt periods
r16
1
0 hrs
10 hrs
1
Duration of melt periods
r17
1
0 min.
30 min.
5
Temperature setting for thermostat band 2
. As differential r01 is used
r21
1
-50°C
50°C
2
Correction of the signal from
S6
r59
1
-10 K
10 K
0
Definition and weighting, if applicable, of thermostat sensors when night cover is on.
(100%=S4, 0%=S3)
r61
1
0 %
100 %
100
S4 min. limit, Frost protection. Cooling is stopped.
r98
1
-50°C
20°C
-50°C
Alarms
Delay for temperature alarm
A03
1
0 min.
240 min.
30
Delay for door alarm
A04
1
0 min.
240 min.
60
Delay for temperature alarm after defrost
A12
1
0 min.
240 min.
90
High alarm limit for thermostat 1
A13
1
-50°C
50°C
8
Low alarm limit for thermostat 1
A14
1
-50°C
50°C
-30
High alarm limit for thermostat 2
A20
1
-50°C
50°C
8
Low alarm limit for thermostat 2
A21
1
-50°C
50°C
-30
High alarm limit for sensor S6 at thermostat 1
A22
1
-50°C
50°C
8
Low alarm limit for sensor S6 at thermostat 1
A23
1
-50°C
50°C
-30
High alarm limit for sensor S6 at thermostat 2
A24
1
-50°C
50°C
8
Low alarm limit for sensor S6 at thermostat 2
A25
1
-50°C
50°C
-30
S6 alarm time delay
With setting = 240 the S6 alarm will be omitted
A26
1
0 min.
240 min.
240
Alarm time delay or signal on the DI1 input
A27
1
0 min.
240 min.
30
Alarm time delay or signal on the DI2 input
A28
1
0 min.
240 min.
30
Signal for alarm thermostat. S4% (100%=S4, 0%=S3)
A36
1
0 %
100 %
100
Delay for S6 (product sensor alarm) after defrost
A52
1
0 min.
240 min.
90
Alarm limit for max. S7 brine temperature
A76
1
-50°C
50°C
8°C
Differential for S7 brine alarm
A77
1
0.1 K
10 K
3.0 K
Compressor
Min. ON-time
c01
1
0 min.
30 min.
0
Min. OFF-time
c02
1
0 min.
30 min.
0
Time delay for cutin of comp.2
c05
1
0 sec
999 sec
5
Compressor 1 on time when sensor fault (compressor 2 = off)
c86
1
0 min
240 min
15
Compressor 1 off time when sensor fault
c87
1
0 min
240 min
15
Defrost
Defrost method
: 0=none, 1= EL
d01
1
0/No
1/EL
1/EL
Defrost stop temperature
d02
1
0°C
50°C
6
Interval between defrost starts
d03
1
0 hrs/Off 240 hrs
8
Max. defrost duration
d04
1
0 min.
360 min.
45
Displacement of time on cutin of defrost at start-up
d05
1
0 min.
240 min.
0