Rail heat control
0=not used, 1=pulse control with timer function (o41 and o42), 2=pulse control 
with dew point function

o85

1

0

2

0

Dew point value where the rail heat is minimum

o86

1

-10°C

50°C

8

Dew point value where the rail heat is 100% on 

o87

1

-9°C

50°C

17

Lowest permitted rail heat effect in % 

o88 

1

0 %

100 %

30

Time delay from "open door” refrigeration is started

o89

1

0 min.

240 min.

30

Definition of readings on lower button:
1=defrost stop sensor,  2=S6 sensor

o92

1

1

2

1

Display of temperature
1= u56 Air temperature
2= u36 product temperature

o97

1

1

2

1

Light and night blinds defined
0: Light is switch off and night blind is open when the main switch is off
1: Light and night blind is independent of main switch

o98

1

0

1

0

Configuration of alarm relay
The alarm relay will be activated upon an alarm signal from the following groups:
1 - High temperature alarms
2 - Low temperature alarms
4 - Sensor error
8 - Digital input is activated for alarm
16 - Defrost alarms
32 - Miscellaneous
The groups that are to activate the alarm relay must be set by using a numerical 
value which is the sum of the groups that must be activated.
(E.g. a value of 5 will activate all high temperature alarms and all sensor errors). 
0 = Cancel relay function

P41

1

0

63

47

Stop time for fan while night blind rolls down

P65

1

0 min.

5 min.

0 min.

Service

Temperature measured with S5 sensor

u09

1

Status on DI1 input. on/1=closed

u10

1

Actual defrost time (minutes)

u11

1

Temperature measured with S3 sensor

u12

1

Status on night operation (on or off) 1=on

u13

1

Temperature measured with S4 sensor

u16 

1

Thermostat temperature

u17

1

Run time of thermostat (cooling time) in minutes

u18

1

Temperature measured with S6 sensor

(product temperature)

u36

1

Status on DI2 output. on/1=closed

u37

1

Display air temperature. Weighted  S3 + S4 (o17)

u56

1

Measured temperature for alarm thermostat. Weighted S3 + S4 (A36)

u57

1

Status on relay for compressor 1

**

u58

1

Status on relay for fan

**

u59 

1

Status on relay for defrost

**

u60

1

Status on relay for rail heat

**

u61

1

Status on relay for alarm

**

u62

1

Status on relay for light

**

u63

1

Status on relay for compressor 2

**

u67

1

Readout of the actual rail heat effect

u85

1

1: Thermostat 1 operating,   2: Thermostat 2 operating

u86

1

Status on high voltage input DI3

u87

1

Readout of thermostats actual cut in value

u90

1

Readout of thermostats actual cut out value

u91

1

Readout of brine temperature S7

u98

1

*) Can only be set when regulation is stopped (r12=0)
**) Can be controlled manually, but only when r12=-1
***)  With access code 2 the access to these menus will be limited

Forced control

If you need to force-control an output, you should set r12 to -1 (manual 
mode). You should then select the relevant relay function, e.g. u58. Go to the 
function by pressing the middle button. Select On.

Continued

code

 1

Min.

Max.

Fac.

Actual

Factory setting

If you need to return to the factory-set values, it can be done in this way:
- Cut out the supply voltage to the controller
- Keep upper and lower button depressed at the same time as you recon-
nect the supply voltage

Factory settings are indicated for standard units. Other code numbers 

have customized settings.

Содержание AK-CC 460

Страница 1: ...Principle Dimensions Instructions AK CC 460 RI8SE202 07 2017 Identification 084B8016 1...

Страница 2: ...her RJ45 For data communication but only if a TCP IP module is inserted in the controller OEM MODBUS For data communication Terminal 56 screen Terminal 57 A Terminal 58 B Alternatively the terminals c...

Страница 3: ...ectly See separate literature No RC8AC Electric noise Cables for sensors DI inputs and data communication must be kept separate from other electric cables Use separate cable trays Keep a distance betw...

Страница 4: ...ion 6 20 AK SM Data communication Display EKA 163 164 L 15 m L 15 m Important All connections to the data communication MODBUS RS 485 and DANBUSS must comply with the requirements for data communicati...

Страница 5: ...arameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to set the value Cutout alarm relay receipt alarm see alarm code A short press of t...

Страница 6: ...Delay for temperature alarm after defrost A12 1 0 min 240 min 90 High alarm limit for thermostat 1 A13 1 50 C 50 C 8 Low alarm limit for thermostat 1 A14 1 50 C 50 C 30 High alarm limit for thermostat...

Страница 7: ...d changeover activate r21 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal 12 night cover 15 appliance shutdown o02 1 0 15 0 Network address 0 off o03 1 0 240 0 On...

Страница 8: ...1 Temperature measured with S3 sensor u12 1 Status on night operation on or off 1 on u13 1 Temperature measured with S4 sensor u16 1 Thermostat temperature u17 1 Run time of thermostat cooling time in...

Страница 9: ...nations Settings from System manager AK SM Settings from AKM AKM destination Send via Network High 1 X Middle 2 X Low 3 X Log only Disabled Operating status Measure ment The controller goes through so...

Отзывы: