6 Programming
6.1 Parameter Descriptions
The parameters in this section are limited to the
parameters required for operating the VLT
®
Advanced
Harmonic Filter AHF 005/AHF 010. For reference to other
parameters, refer to the frequency converter programming
guide.
5-00 Digital I/O Mode
Digital inputs and programmed digital outputs are pre-
programmable for operation either in PNP or NPN systems.
Option:
Function:
NOTICE
Perform a power cycle to
activate the parameter once it
has been changed.
[0]
*
PNP
Action on positive directional pulses
(↕)
. PNP systems are pulled down
to GND.
[1]
NPN
Action on negative directional
pulses
(↕)
. NPN systems are pulled
up to +24 V, internally in the
frequency converter.
5-01 Terminal 27 Mode
Option:
Function:
NOTICE
This parameter cannot be
adjusted while the motor is
running.
[0]
*
Input
Defines terminal 27 as a digital
input.
[1]
Output
Defines terminal 27 as a digital
output.
5-02 Terminal 29 Mode
Option:
Function:
NOTICE
This parameter is available for
FC 302 only.
[0]
*
Input
Defines terminal 29 as a digital
input.
[1]
Output
Defines terminal 29 as a digital
output.
6.1.1 5-1* Digital Inputs
The digital inputs are used for selecting various functions
in the frequency converter.
shows which functions
can be assigned to digital inputs.
Functions in group 1 have higher priority than functions in
group 2.
Group 1
Reset, coast stop, reset, and coast stop, quick stop,
DC brake, stop, and the [Off] key.
Group 2
Start, latched start, reversing, start reversing, jog,
and freeze output.
Table 6.1 Function Groups
Digital input function
Select
Terminal
No operation
[0]
All, terminal 32, 33
Reset
[1]
All
Coast inverse
[2]
All, terminal 27
Coast and reset inverse
[3]
All
Quick stop inverse
[4]
All
DC brake inverse
[5]
All
Stop inverse
[6]
All
Start
[8]
All, terminal 18
Latched start
[9]
All
Reversing
[10]
All, terminal 19
Start reversing
[11]
All
Enable start forward
[12]
All
Enable start reverse
[13]
All
Jog
[14]
All, terminal 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Speed down
[22]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Precise stop inverse
[26]
18, 19
Precise start, stop
[27]
18, 19
Catch up
[28]
All
Slow down
[29]
All
Counter input
[30]
29, 33
Pulse input edge
triggered
[31]
29, 33
Pulse input time based
[32]
29, 33
Ramp bit 0
[34]
All
Ramp bit 1
[35]
All
Programming
Design Guide
MG80C602
Danfoss A/S © 05/2019 All rights reserved.
39
6
6