2 Installation

2.1 Safety Information

N O T I C E

QUALIFIED PERSONNEL

Only qualified, Danfoss authorized personnel are allowed to install the parts described in these installation instructions.

Disassembly and reassembly of the frequency converter must be done in accordance with the service guide.
Use the standard fastener torque values from the service guide, unless the torque value is specified in these instructions.

W A R N I N G

ELECTRICAL SHOCK HAZARD

Danfoss frequency converters contain dangerous voltages when connected to mains voltage. Improper installation, and instal-
ling or servicing with power connected, can cause death, serious injury, or equipment failure.

Only use qualified electricians for the installation.
Disconnect the frequency converter from all power sources before installation or service.
Treat the frequency converter as live whenever the mains voltage is connected.
Follow the guidelines in these instructions and local electrical safety codes.

W A R N I N G

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not pow-
ered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait the specified time after
power has been removed before performing service or repair work can result in death or serious injury.

Stop the motor.
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to other
frequency converters.
Disconnect or lock the motor.
Disconnect any brake option.
Disconnect any regen/load share option.
Wait for the capacitors to discharge fully. The minimum waiting time is listed on the frequency converter label and also in the
following discharge time table.
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the capacitors
are fully discharged.

Table 4: Discharge Time

Frame

Minimum waiting time

D1h–D8h

20 minutes

Fx09–Fx10

20 minutes

E1h–E4h

40 minutes

Fx11–Fx12

40 minutes

AN389655468601en-000101 / 130R0767

2 | Danfoss A/S © 2022.03

Installation

Top Fan Kit for FA09-FA12/D3h-D4h/E3h-E4h

Application Guide

Содержание 176F3167

Страница 1: ...Table 1 Top Fan Kits for iC7 Series FA09 FA12 Frequency Converters Kit number Description Frame designation 176F3167 Top fan IP20 DC 80x38 mm FA09 FA10 176F6636 Top fan IP20 DC 120x38 mm 48 V DC FA11...

Страница 2: ...N G DISCHARGE TIME The frequency converter contains DC link capacitors which can remain charged even when the frequency converter is not pow ered High voltage can be present even when the warning LED...

Страница 3: ...5 Removing the Top Fan and Single Fan Housing 2 7 Removing the Top Fan and Double Fan Housing 2 3 Removing the Top Fan and Grill To remove the top fan and grill use the following steps See Illustratio...

Страница 4: ...le access hole on the top of the frequency converter Reconnect the in line fan cable connector Position the fan on top of the frequency converter with the air direction arrows pointing upward and away...

Страница 5: ...ng To install the top fan and single fan housing use the following steps Feed the top fan cable through the cable access hole on the top of the frequency converter Reconnect the in line fan cable conn...

Страница 6: ...Fan and Double Fan Housing To replace the top fan and double fan housing use the following steps Place 2 fans over the pins in the double fan housing Check that the air direction arrows point upward...

Страница 7: ...AN389655468601en 000101 130R0767 7 Danfoss A S 2022 03 Installation Top Fan Kit for FA09 FA12 D3h D4h E3h E4h Application Guide...

Страница 8: ...in a quotation or order confirmation Danfoss cannot accept any responsibility for possible errors in catalogues brochures videos and other material Danfoss reserves the right to alter its products wi...

Отзывы: