4-20 mA Analog Output 

 MCD 

Remote 

Operator 

 

MG.17.E5.02 - VLT

®

 is a registered Danfoss trademark 

10 

5.5.

 

Programmable Parameters 

The Remote Operator offers the following programmable parameters: 

Parameter 
Number 

Description 

Default 
Setting 

Adjustable Range 

RS485 network 
baud rate 

(9600 baud)

2 = 2400 baud 
3 = 4800 baud 
4 = 9600 baud 
5 = 19200 baud 
6 = 38400 baud 

RS485 network 
satellite address 

20 

1 to 99 

RS485 network 
timeout 

0 seconds 

(= off) 

0 to 100 seconds 

RS485 network 
protocol 

(AP ASCII) 

1 = AP ASCII protocol 
2 = Modbus RTU protocol 

Modbus protocol 
parity 

(no parity) 

0 = no parity 
1 = odd parity 
2 = even parity 
3 = 10-bit transmission 

Motor FLC (A) 

10 

1 to 2868 

Analog output 
4 mA offset (%) 

100 

80 to 120 

Start, Stop, 
Quick stop 
function disable 

0 = Remote Operator and Network start, stop, quick stop 
function enabled. 
1 = Remote Operator start, stop, quick stop function enabled. 
Network start, stop, quick stop function disabled. 

 

2 = Remote Operator start, stop, quick stop function disabled. 
Network start, stop, quick stop function enabled.   
3 = Remote Operator start, stop, quick stop function disabled. 
Network start, stop, quick stop function disabled. 

,

  

 

9 Current 

÷

 10 

0 = off (required for models MCD5-0084B ~ MCD5-1600C) 
1 = on (required for models MCD5-0021B ~ MCD5-0068B) 

Pars. 1 to 5 only apply when the Remote Operator is being used as a Modbus or AP ASCII network 
gateway.  => the Modbus Module Instructions for details. 

  Remote Operator Reset pushbutton is always enabled. 

  RS485 Network reset and forced communication trip functions are always enabled. 

 

N.B.!:

 

Remote Operator Par. 9 

Current 

÷

 10

  normalises the displayed motor current and analog 

output for models MCD5-0021B ~ MCD5-0068B.  Use Par. 9 in conjunction with Par. 6 

Motor 

FLC

 as follows: 

1.

 

Set Par. 6 to a value 10 times greater than the actual motor nameplate FLC (e.g. for 

actual FLC = 4.6 A, set Par. 6 to 46). 

2.

 

Set Par. 9 = 1. 

 

 

Содержание 175G9004

Страница 1: ...actice for RS485 communications when installing and using this equipment 1 2 General Description The Remote Operator can be used with MCD 200 MCD 3000 and MCD 500 soft starters and offers the followin...

Страница 2: ...Remote Operator through the cutout and locate the mounting bracket at the rear of the panel onto the four studs Use the four fasteners to tighten the mounting bracket up to the rear of the panel For u...

Страница 3: ...177HA264 11 Remove mains and control voltage from the soft starter before attaching or removing accessories Failure to do so may damage the equipment Once the Remote Operator Module has been installed...

Страница 4: ...lows 1 Protocol AP ASCII 2 Address 20 3 Baud Rate 9600 4 Parity No parity 5 Timeout No timeout 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 16 8 4 2 1 0 0 0 0 0 DIP SWITCH A DIP SWITCH B 177HA543 10 1 2 3 4 5 4 Appl...

Страница 5: ...starter 177HA375 10 MCD 3000 REMOTE OPERATOR RS485 SERIAL PORT 68 61 69 B1 B2 B3 B6 B7 B8 GND RS485 STARTER RS485 NETWORK 4 20 mA ANALOGUE OUTPUT MOTOR CURRENT B10 B11 4 20 mA SUPPLY VOLTAGE 18 30 VA...

Страница 6: ...Interface AP ASCII protocol as standard Connection Terminals B1 B2 B3 3 pole spring clamp connector terminals Analog Output Motor Current Monitoring Interface 4 20 mA max burden 200 Connection Termin...

Страница 7: ...h the serial communications network if connected on the network side of the Remote Operator SOFT STARTER START STOP DATA PROG RESET START RUN TRIP RS485 AMPS TEMP CODE Stop Pushbutton Start Pushbutton...

Страница 8: ...and 1 11 instead of motor temperature N B When using the Remote Operator with MCD 500 models MCD5 0023B MCD5 0068B the motor current and analog output must be normalised using Pars 6 and 9 Programmab...

Страница 9: ...rameter Parameter 7 This is set to give a 4 mA output signal when the motor current is zero The 4 20 mA analog output has an accuracy of 10 It is not designed for process signal control use and should...

Страница 10: ...mote Operator start stop quick stop function enabled Network start stop quick stop function disabled 2 Remote Operator start stop quick stop function disabled Network start stop quick stop function en...

Страница 11: ...5 LED flashing The Remote Operator has detected a loss of communication on the RS485 link to the soft starter Verify and solve the cause for loss of communication If communication is restored before t...

Отзывы: