MCD Remote Operator 

 Troubleshooting 

 

MG.17.E5.02 - VLT

®

 is a registered Danfoss trademark 

11 

6.

 

Troubleshooting 

6.1.

 

Feedback 

The Remote Operator Display and Status LEDs can indicate abnormal operating or system conditions. 
This troubleshooting guide gives details of these conditions. 

Display Indication 

Cause 

Possible Solution 

No display 

No control supply voltage 

Check that correct voltage is present at terminals 1, 2. 

AMPS or TEMP 
LED flashing 

Soft starter in restart delay 
mode 

Wait for the restart delay (programmed in the soft 
starter) to elapse. 

AMPS, TEMP and CODE 
LEDs on 

The Remote Operator is in 
Program mode 

The Remote Operator cannot control the starter until 
Program mode is closed. 

 

The MCD 500 is not in status 
mode 

The Remote Operator can start the motor; this will 
return the soft starter to status mode. 

Four dashes on display 
and RS485 LED flashing 

The Remote Operator has 
detected a loss of 
communication on the RS485 
link to the soft starter 

Verify and solve the cause for loss of communication.  
If communication is restored before the soft starter 
trips, the display will return to active status and the 
RS485 LED will illuminate. If communication is 
restored after the soft starter has tripped, the display 
will indicate the trip code. Use the Reset pushbutton 
to reset the soft starter fault. 

Incorrect or no 4-20 mA 
analog output signal 

Check the correct voltage is present at terminals 1, 2. 
Check that correct polarity is used at terminals B10, 
B11. 
Check that the Motor FLC, Analog Output 4 mA Offset 
and Current 

÷

 10 parameters are set correctly. 

The motor cannot be started  Check that control voltage is connected to the starter.  

 

If connected to an MCD 200 , check that terminals 
A1-N2 on the starter are linked. 

 

If connected to an MCD 500, check that terminals 
17 and 25 to 18 are linked and the starter is in 
Auto On mode.   

Parameter 8 on the Remote Operator must be set to 0 
or 1 

 

  
 

Содержание 175G9004

Страница 1: ...actice for RS485 communications when installing and using this equipment 1 2 General Description The Remote Operator can be used with MCD 200 MCD 3000 and MCD 500 soft starters and offers the followin...

Страница 2: ...Remote Operator through the cutout and locate the mounting bracket at the rear of the panel onto the four studs Use the four fasteners to tighten the mounting bracket up to the rear of the panel For u...

Страница 3: ...177HA264 11 Remove mains and control voltage from the soft starter before attaching or removing accessories Failure to do so may damage the equipment Once the Remote Operator Module has been installed...

Страница 4: ...lows 1 Protocol AP ASCII 2 Address 20 3 Baud Rate 9600 4 Parity No parity 5 Timeout No timeout 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 16 8 4 2 1 0 0 0 0 0 DIP SWITCH A DIP SWITCH B 177HA543 10 1 2 3 4 5 4 Appl...

Страница 5: ...starter 177HA375 10 MCD 3000 REMOTE OPERATOR RS485 SERIAL PORT 68 61 69 B1 B2 B3 B6 B7 B8 GND RS485 STARTER RS485 NETWORK 4 20 mA ANALOGUE OUTPUT MOTOR CURRENT B10 B11 4 20 mA SUPPLY VOLTAGE 18 30 VA...

Страница 6: ...Interface AP ASCII protocol as standard Connection Terminals B1 B2 B3 3 pole spring clamp connector terminals Analog Output Motor Current Monitoring Interface 4 20 mA max burden 200 Connection Termin...

Страница 7: ...h the serial communications network if connected on the network side of the Remote Operator SOFT STARTER START STOP DATA PROG RESET START RUN TRIP RS485 AMPS TEMP CODE Stop Pushbutton Start Pushbutton...

Страница 8: ...and 1 11 instead of motor temperature N B When using the Remote Operator with MCD 500 models MCD5 0023B MCD5 0068B the motor current and analog output must be normalised using Pars 6 and 9 Programmab...

Страница 9: ...rameter Parameter 7 This is set to give a 4 mA output signal when the motor current is zero The 4 20 mA analog output has an accuracy of 10 It is not designed for process signal control use and should...

Страница 10: ...mote Operator start stop quick stop function enabled Network start stop quick stop function disabled 2 Remote Operator start stop quick stop function disabled Network start stop quick stop function en...

Страница 11: ...5 LED flashing The Remote Operator has detected a loss of communication on the RS485 link to the soft starter Verify and solve the cause for loss of communication If communication is restored before t...

Отзывы: