Installation 

 MCD 

Remote 

Operator 

 

MG.17.E5.02 - VLT

®

 is a registered Danfoss trademark 

2.6.

 

For use with MCD 500 

In order to use the Remote Operator with MCD 500 soft starters, a Modbus Module must first be installed 
to the starter using the following steps: 

1.

 

 Remove control power and mains supply from the soft starter. 

2.

 

Attach the Modbus Module to the side of the starter as illustrated. 

17

7

H

A

5

31

.1

0

 

 

Remove mains and control voltage from the soft starter before attaching or removing 
accessories. Failure to do so may damage the equipment. 

3.

 

 The DIP switches on the Modbus Module must be set as follows: 

 

 

Protocol = AP ASCII 

Address = 20 

Baud Rate = 9600 

Parity = No parity 

Timeout = No timeout 

123456

ON

123456

ON

+16

+8

+4

+2

+1

0

0

0

0

0

DIP S

W

ITCH A

DIP S

W

ITCH B

177HA543.10

1

2

3

4

5

 

 

 

4.

 

Apply control power to the soft starter.  The LED on the Modbus module should flash. 

5.

 

In order for the MCD 500 to accept commands from the serial network, the soft starter must be 
in Auto On mode and links must be fitted to terminals 17 and 25 to 18. 

6.

 

Connect the RS485 cable between the Remote Operator and the Modbus Module.  Apply 
control voltage to the Remote Operator. 

177HA535.

10

MCD 500

(Auto On mode)

REMOTE OPERATOR

RS485

Serial Port

B8 B7 B6

B1

B2

B3

B6 B7 B8

RS485

RS485

4-20 mA

Analog Output

B10 B11

4-20 mA

Supply Voltage

18~30 VAC/VDC

1

2

PO

+  GND  -

-  GND  +

-  GND  +

+     -

~/+  ~/-

MODBUS MODULE

17

18

25

Stop

COM

Reset

 

Содержание 175G9004

Страница 1: ...actice for RS485 communications when installing and using this equipment 1 2 General Description The Remote Operator can be used with MCD 200 MCD 3000 and MCD 500 soft starters and offers the followin...

Страница 2: ...Remote Operator through the cutout and locate the mounting bracket at the rear of the panel onto the four studs Use the four fasteners to tighten the mounting bracket up to the rear of the panel For u...

Страница 3: ...177HA264 11 Remove mains and control voltage from the soft starter before attaching or removing accessories Failure to do so may damage the equipment Once the Remote Operator Module has been installed...

Страница 4: ...lows 1 Protocol AP ASCII 2 Address 20 3 Baud Rate 9600 4 Parity No parity 5 Timeout No timeout 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON 16 8 4 2 1 0 0 0 0 0 DIP SWITCH A DIP SWITCH B 177HA543 10 1 2 3 4 5 4 Appl...

Страница 5: ...starter 177HA375 10 MCD 3000 REMOTE OPERATOR RS485 SERIAL PORT 68 61 69 B1 B2 B3 B6 B7 B8 GND RS485 STARTER RS485 NETWORK 4 20 mA ANALOGUE OUTPUT MOTOR CURRENT B10 B11 4 20 mA SUPPLY VOLTAGE 18 30 VA...

Страница 6: ...Interface AP ASCII protocol as standard Connection Terminals B1 B2 B3 3 pole spring clamp connector terminals Analog Output Motor Current Monitoring Interface 4 20 mA max burden 200 Connection Termin...

Страница 7: ...h the serial communications network if connected on the network side of the Remote Operator SOFT STARTER START STOP DATA PROG RESET START RUN TRIP RS485 AMPS TEMP CODE Stop Pushbutton Start Pushbutton...

Страница 8: ...and 1 11 instead of motor temperature N B When using the Remote Operator with MCD 500 models MCD5 0023B MCD5 0068B the motor current and analog output must be normalised using Pars 6 and 9 Programmab...

Страница 9: ...rameter Parameter 7 This is set to give a 4 mA output signal when the motor current is zero The 4 20 mA analog output has an accuracy of 10 It is not designed for process signal control use and should...

Страница 10: ...mote Operator start stop quick stop function enabled Network start stop quick stop function disabled 2 Remote Operator start stop quick stop function disabled Network start stop quick stop function en...

Страница 11: ...5 LED flashing The Remote Operator has detected a loss of communication on the RS485 link to the soft starter Verify and solve the cause for loss of communication If communication is restored before t...

Отзывы: