Instruction CF-MC Master Controller
12
VI.UH.K2.80
Produced by Danfoss Floor Heating Hydronics 01.2006
8. Specifi cations
Transmission frequency
868.42MHz
Transmission Range
In normal constructions (up to)
30m
Transmission power
<1mW
Supply Voltage
230V a.c.
Actuator outputs
10 x 24V d.c.
Max. continued output load (total)
35VA
Relays
230V a.c./8 (2) A
Ambient temperature
0-50°C
IP class
30
Error indication
Possible Causes
Output LED(s), alarm LED
and output menu LED
fl ash. Buzzer is ON*
Output or actuator is short-circuited or
the actuator is disconnected
Output LED(s), alarm
LED and input menu LED
fl ash. Buzzer ON after 12
hours**
No wireless signal from Room Thermostat
connected to this or these outputs or the
temperature in the according room is be-
low 5°C. (Try to verify the function of the
room thermostat by making a link test)
Output LEDs 1-4, alarm
LED and input LED fl ash
No signal from the Remote Controller
Output LEDs 1-5, alarm
LED and input menu LED
fl ash
No signal from Master Controller #2 or #3
* Buzzer is shut off by pressing OK. The error indication continues until the error
is fi xed
** If the Room Thermostat signal is lost, the Master Controller output will be
activated 15 minutes every hour for frost protection until the error is fi xed
9. Troubleshooting
Содержание 088U0200
Страница 3: ...Instruction CF MC Master Controller 2 VI UH K2 80 Produced by Danfoss Floor Heating Hydronics 01 2006...
Страница 55: ...54 VI UH K2 80 Tillverkad av Danfoss Floor Heating Hydronics 01 2006 Bruksanvisning CF MC masterregulator...
Страница 56: ...Fig 1 Fig 2 a b c d e A1...
Страница 57: ...Fig 3 Fig 4 Fig 5 Fig 6 Fig 7 Fig 8 Fig 9 Fig 10 Fig 11 click click A2...
Страница 58: ...Fig 12 Fig 13 Fig 14 Fig 15 Fig 16 Fig 19 Fig 17 Fig 18 Fig 20 B1...
Страница 59: ...Fig 24 Fig 22 Fig 26 Fig 21 Fig 23 Fig 25 B2...
Страница 60: ...088N2459 06 01 2006 Version 03...