Instruction CF-MC Master Controller
9
VI.UH.K2.80
Produced by Danfoss Floor Heating Hydronics 01.2006
6.2 Relays for Pump & Boiler Control
Activate Relay mode on Master Controller (fi g. 23)
•
Use the menu selection button to select the Relay mode. Relay LED
fl ashes
•
Activate Relay mode by pressing OK . Relay LED goes ON
Select the Relay confi guration
•
Press the output selection button and toggle between the possible
Relay confi gurations - the output LEDs will be ON – indicated below:
•
NO LEDs: The relays are not used
•
1 LED: Pump control
•
2 LEDs: Boiler control
•
3 LEDs: Pump and boiler control
•
4 LEDs: Pump control with 2min. start/stop delay
•
5 LEDs: Pump and boiler control, with 2min. start/stop delay on pump
(default)
•
Activate selected relay confi guration by pressing OK
Note: If the pump relay is active, the Master Controller will run a pump motion
program every 3rd day and it will last for one minute.
6.3 Input for Global Standby and Heating & Cooling
Activate Input mode on Master Controller (fi g. 23)
•
Use the menu selection button to select the Input mode. Input LED
fl ashes
•
Activate Input mode by pressing OK . Input LED goes ON
Select the Input confi guration
•
Press the output selection button and toggle between the possible
Input confi gurations - the output LEDs will be ON – indicated below:
•
1 LED: The input ports are not used
•
2 LEDs: The Master Controller will switch to cooling mode when the input
for heating/cooling is activated (fi g. 2 - )
•
3 LEDs: The Master Controller will switch to a fi xed set room temperature
at 8 °C for all Room Thermostats when the input for global standby is
activated (fi g. 2 - )
•
4 LEDs: The Master Controller will switch to cooling mode when the input
for heating/cooling is activated (fi g. 2 - ). In heating mode the Master
Controller will switch to a fi xed set room temperature at 8 °C for all Room
Thermostats when the input for global standby is activated (fi g. 2 - )
(default)
•
Activate selected input confi guration by pressing OK
Содержание 088U0200
Страница 3: ...Instruction CF MC Master Controller 2 VI UH K2 80 Produced by Danfoss Floor Heating Hydronics 01 2006...
Страница 55: ...54 VI UH K2 80 Tillverkad av Danfoss Floor Heating Hydronics 01 2006 Bruksanvisning CF MC masterregulator...
Страница 56: ...Fig 1 Fig 2 a b c d e A1...
Страница 57: ...Fig 3 Fig 4 Fig 5 Fig 6 Fig 7 Fig 8 Fig 9 Fig 10 Fig 11 click click A2...
Страница 58: ...Fig 12 Fig 13 Fig 14 Fig 15 Fig 16 Fig 19 Fig 17 Fig 18 Fig 20 B1...
Страница 59: ...Fig 24 Fig 22 Fig 26 Fig 21 Fig 23 Fig 25 B2...
Страница 60: ...088N2459 06 01 2006 Version 03...