Page 26 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
DEHUMIDIFICATION
MODE
a)
MTV2,
AUX1
and
heater
are
always
off.
b)
If
Tr
≥
25ºC,
then
MTV1
and
AUX2
will
be
ON
for
3
minutes,
and
then
OFF
for
4
minutes.
c)
If
16ºC
≤
Tr
<
25ºC,
then
MTV1
and
AUX2
will
be
ON
for
3
minutes,
and
then
OFF
for
6
minutes.
d)
If
Tr
<
16ºC,
then
MTV1
and
AUX2
will
be
turned
off
for
4
minutes.
e)
At
the
end
of
the
above
dehumidification
cycle,
the
system
will
decide
the
next
dehumidification
control
option.
Indoor
fan
will
run
at
low
speed
throughout
the
dehumidification
process.
AUTOMODE
Without
Electric
heater
and
With
Electric
Heater
as
Booster
a)
Every
time
the
unit
is
turned
on,
MTV1
is
on
while
AUX1,
AUX2
and
fan
are
off.
MTV2
and
the
heater
are
always
off.
After
120
seconds,
the
subsequent
operation
mode
is
decided
according
to
the
following:
1)
If
the
coil
temperature
sensor
(Ti1)
≥
36°C,
then
MTV1,
AUX1
and
fan
turn
on
or
off
according
to
HEAT
mode.
2)
If
Ti1
<
36°C,
then
MTV1,
AUX2
and
fan
turn
on
or
off
according
to
COOL
mode.
b)
Unit
remains
in
AUTO
COOL
or
AUTO
HEAT
mode
throughout
the
operating
cycle
until
the
user
changes
the
mode
manually
or
restarts
the
unit.
c)
Should
the
Ti1
sensor
fail
or
be
damaged,
auto
mode
will
not
function.
With
Electric
Heater
as
Primary
Heat
Source
a)
If
the
current
running
mode
is
AUTO
COOL
mode,
it
will
change
over
to
AUTO
HEAT
mode
upon
satisfying
all
the
conditions
below:
1)
Ts
‐
Tr
≥
1°C
(or
–
4ºC
if
economy
contact
is
activated).
2)
MTV1
has
stopped
≥
10
minutes.
b)
If
the
current
running
mode
is
AUTO
HEAT
mode,
it
will
change
over
to
AUTO
COOL
mode
upon
satisfying
all
the
conditions
below:
1)
Tr
‐
Ts
≥
1°C
(or
+
4ºC
if
economy
contact
is
activated).
2)
MTV1
has
stopped
≥
10
minutes.
Note:
AUTO
COOL
or
AUTO
HEAT
operations
are
the
same
as
COOL
or
HEAT
mode
respectively.
C.1.5.2.
Without
Thermoelectric
Valve
Configuration
COOL
MODE
a)
Heater,
AUX1,
MTV1
and
MTV2
are
always
off.
b)
If
Tr
≥
Ts
+
1ºC
(or
+
4ºC
if
economy
contact
is
activated),
then
cool
operation
is
activated
and
AUX2
is
turned
on.
Indoor
fan
runs
at
set
speed.
c)
If
Tr
<
Ts,
then
cool
operation
is
terminated
and
AUX2
is
off.
Indoor
fan
is
turned
off.
d)
The
range
of
Ts
is
16
‐
30ºC.
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
f)
When
the
unit
is
turned
off,
indoor
fan
shut
down
after
5
seconds.
LOW
TEMPERATURE
PROTECTION
OF
INDOOR
COIL
a)
If
Ti1
≤
2ºC
for
2
minutes,
then
AUX2
is
turned
off.
If
low
speed
is
selected
via
user
interface,
then
indoor
fan
runs
at
medium
speed.
If
medium
or
high
speed
is
selected
via
user
interface,
then
indoor
fan
runs
at
set
speed.
b)
If
Ti1
≥
5ºC
for
2
minutes,
then
AUX2
is
turned
on.
Indoor
fan
runs
at
set
speed.
Содержание FMCD*ECM series
Страница 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Страница 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Страница 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Страница 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...