Page 24 of 62
SK2014
‐
SON
‐
002
‐
TechMnl
‐
FMCD
‐
003
C.1.5.
Control
Logics
for
2
‐
Pipe
System
C.1.5.1.
With
Thermoelectric
Valve
Configuration
COOL
MODE
a)
MTV2,
AUX1
and
electric
heater
are
always
off.
b)
If
Tr
≥
Ts
+
1ºC
(or
+
4ºC
if
economy
contact
is
activated),
then
cool
operation
is
activated
and
MTV1
and
AUX2
are
turned
on.
Indoor
fan
runs
at
set
speed.
c)
If
Tr
<
Ts,
then
cool
operation
is
terminated
and
MTV1
and
AUX2
are
turned
off.
Indoor
fan
runs
at
set
speed.
d)
The
range
of
Ts
is
16
‐
30ºC
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
f)
When
turned
on,
MTV1
requires
30
seconds
before
it
is
fully
open.
g)
When
turned
off,
MTV1
requires
120
seconds
before
it
is
fully
closed.
h)
When
the
unit
is
turned
off,
the
indoor
fan
will
shut
down
after
5
seconds.
LOW
TEMPERATURE
PROTECTION
OF
INDOOR
COIL
a)
If
Ti1
≤
2
ºC
for
2
minutes,
then
MTV1
and
AUX2
are
turned
off.
If
indoor
fan
is
set
for
low
speed,
then
it
will
run
at
medium
speed.
If
it
is
set
at
medium
or
high
speed,
then
it
will
keep
running
at
the
same
speed.
b)
If
Ti1
≥
5ºC
for
2
minutes,
then
MTV1
and
AUX2
are
turned
on.
Indoor
fan
runs
at
set
speed.
FAN
MODE
a)
Indoor
fan
runs
at
the
set
speed
while
heater,
MTV1,
MTV2,
AUX1
and
AUX2
are
turned
off.
b)
Indoor
fan
speed
can
be
adjusted
to
low,
medium
and
high.
HEAT
MODE
Without
Electrical
Heater
a)
MTV2,
AUX2
and
electric
heater
are
always
off.
b)
If
Tr
≤
Ts
‐
1
ºC
(or
‐
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
MTV1
and
AUX1
are
turned
on.
Indoor
fan
runs
at
the
set
speed.
c)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
MTV1
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200rpm.
d)
The
range
of
Ts
is
16
‐
30ºC.
e)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
f)
When
turned
on,
MTV1
requires
30
seconds
before
it
is
fully
open.
g)
When
turned
off,
MTV1
requires
120
seconds
before
it
is
fully
closed.
With
Electrical
Heater
as
Booster
a)
MTV2
and
AUX2
are
always
off.
b)
If
Tr
≤
Ts
‐
1ºC
(or
‐
4ºC
if
economy
contact
is
activated),
then
heat
operation
is
activated
and
MTV1
and
AUX1
are
turned
on.
Indoor
fan
runs
at
the
set
speed.
c)
If
Tr
>
Ts,
then
heat
operation
is
terminated
and
MTV1
and
AUX1
are
turned
off.
Indoor
fan
runs
at
200rpm
d)
If
Ti1
<
40ºC,
then
the
electrical
heater
is
turned
on.
If
40ºC
≤
Ti1
<
45ºC,
then
the
electrical
heater
maintains
its
original
state.
If
Ti1
≥
45ºC,
then
the
electrical
heater
is
turned
off.
e)
The
range
of
Ts
is
16
‐
30ºC
f)
Indoor
fan
speed
can
be
adjusted
to
low,
medium,
high
and
auto.
g)
When
turned
on,
MTV1
requires
30
seconds
before
it
is
fully
open.
h)
When
turned
off,
MTV1
requires
120
seconds
before
it
is
fully
closed.
Содержание FMCD*ECM series
Страница 11: ...Page 11 of 62 Dimensional drawing for FMCD 20 24 ECM All dimensionsshown in mm ...
Страница 21: ...Page 21 of 62 SK2014 SON 002 TechMnl FMCD 003 C 1 3 Wiring Diagram SK NCFMCD 001 ...
Страница 45: ...Page 45 of 62 SK2014 SON 002 TechMnl FMCD 003 C 4 2 Wiring Diagram SK NCFMCD 002 ...
Страница 62: ...Page 62 of 62 SK2014 SON 002 TechMnl FMCD 003 ...