Page
68
of 77
SK2019 FCSD(H)-V/P-ECM-001
Control Logic Specifications
Unit Power ON/OFF
a)
The unit is turned ON when any of the fan speed inputs (H/M/L) are ON, or modulating signal input is more than 2.0 VDC.
b)
The unit is turned OFF only if all of the fan speed inputs (H/M/L) are OFF and modulating signal input is less than 2.0 VDC.
Alarm Protection and Error Display
a)
If the float switch is open for 5 minutes or EC motor is failed, then the (NC) voltage-free alarm contact shall be opened
and the (NO) voltage free alarm contact shall be closed.
b)
If the float switch is open for 10 minutes, the LED display reports a condensate management failure (see table on the
next page).
Drain Pump Operation
a)
When the unit turns ON:
i.
If Ti1 < 14ºC, the drain pump turns ON.
ii.
If 14ºC<=Ti<16ºC, the drain pan keeps original state.
iii.
If Ti1 ≥ 16 ºC, the drain pump turns OFF.
b)
When the unit turns OFF, the drain pump will remain ON for 5 minutes and then turn OFF.
c)
At any time:
i.
If the float switch is OPEN, the drain pump will turn ON.
ii.
If the float switch is OPEN and then CLOSED, the drain pump will remain ON for 5 minutes, and then turn OFF.
Louver Control
a)
When the unit is OFF, the louvers are closed (angle at 100º against vertical).
b)
When the unit turns ON, the louvers open (angle at 87º against the horizontal).
c)
When the unit turns OFF, the louvers return to a closed position (100º against the vertical).
Modulating Signal Input
a)
The standard configuration is for 0~5 VDC modulating signal input.
b)
The optional configuration is for 0~10 VDC modulating signal. To set the PCB to the optional configuration, the S1 jumper
must be closed.
Low Temperature Protection of Indoor Coil in Winter
This is frost protection for when the unit is off to prevent water in the coil and room from freezing.
Unit is in Standby Mode
If Ti1
≦
2 ºC for 2 minutes, report error code and Buzzer is beeping for 3 minutes.
Содержание FDLA-09
Страница 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Страница 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Страница 53: ...FDHD V P AC MOTOR...
Страница 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Страница 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Страница 76: ...Configuration Settings D 3...
Страница 111: ......
Страница 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Страница 140: ...Page 28 of 77 SK2019 FCSD H V P ECM 001 For 2 pipe system with modulating valve For 4 pipe systems with modulating valve...
Страница 190: ...SK2019 FCSD H V P ECM 001...
Страница 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Страница 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Страница 231: ...Page 41 of 59 SK2015 SWC V EC 001 D 3 4 Unit Network Wiring Scheme Wiring diagram for a master slave network connection...
Страница 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Страница 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Страница 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Страница 250: ...FSTD C V P ECM MOTOR...
Страница 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...
Страница 278: ...Page 29 of 73 SK2015 FSTDC V P ECM 001 C 2 Wiring Diagram SK NCPFWB 001 ECM S Configuration Full Control PCB...
Страница 305: ...Page 56 of 73 SK2015 FSTDC V P ECM 001 E 4 Wiring Diagrams E 4 1 Standard Unit Wiring Diagram of SK NCPFWB 002 ECM...
Страница 322: ...Page 73 of 73 SK2015 FSTDC V P ECM 001...