DAITEM SH148AX Скачать руководство пользователя страница 9

GB

23

The detector’s overall range is determined by
the lower beam range.
• The 

upper beam

must always be parallel

to the ground

• The 

lower beam

must be adjusted in

relation to the position of the lower lens (2
m or 5 m mark).

• Given that the 2 beams must be

simultaneously broken to trigger an alarm,
the detector range is limited to the lower
beam range as shown in the diagram
below.

7. Detection settings and configuration

7.1 Detection range

IMPORTANT
• The 2 m or 5 m indications on the product

should only be used to help position the
lower lens.

• To determine the detection range, please

refer to the tables above.

d

1. 

Unscrew and open the front panel.

2. 

Unclip the lower lens and rotate it 180°
before repositioning it.

.

Inside front panel

Lower 
lens

Upper lens

Detection table for lower lens set
at 5 m

• The lower lens is factory-positioned for

detection at 5 m. If 2 m detection is
required:

• The detection range is determined by the

lower lens setting and the detector
installation height.

* Detection range data may vary in relation to atmospheric

conditions.

Installation
height (m)

0.8 0.9

1

1.1 1.2

Detection range
(m)*

6

7

7.5

8

8.5

Detection table for lower lens 
set at 2 m

* Detection range data may vary in relation to atmospheric

conditions.

Installation
height (m)

0.8 0.9

1

1.1 1.2

Detection range
(m)*

3

3.5 3.7

4

4.2

A. no detection: 

only the lower beam is broken.

B. detection: 

the lower and upper beams are

broken.

C. no detection:

only the upper beam is broken.

C

B

A

IMPORTANT: do not
remove the upper lens

Содержание SH148AX

Страница 1: ......

Страница 2: ...the radio link 22 6 2 Fixing the detector in place 22 7 Detection settings and configuration 23 7 1 Detection range 23 7 2 Adjusting the detection angle horizontally 25 7 3 Setting the operating opti...

Страница 3: ...rantee sticker Test button Programming LED Lithium battery Tamper tab Detection module Upper detection beam Lower detection beam LED indicator Tamper tab Locking mechanism Dip switches for operating o...

Страница 4: ...oughly 2 s 2 Guarantee sticker Remove the pre cut part of the sticker and stick it to the guarantee certi cate in the user manual supplied with the control panel If you are adding to an existing syste...

Страница 5: ...to enter then IMPORTANT the control panel issues three short beeps to indicate a programming error When this happens programming must be performed again from the beginning Press then on the control p...

Страница 6: ...until the LED briefly goes out Press the button 1 to 4 times for the parameter value To end press and hold the button until the LED goes out Programming LED steadily lit parameter set correctly Start...

Страница 7: ...o metres away from other devices except other detectors The detector must not be placed in a location where the detection beams are likely to be directly or indirectly impacted by the sun s rays or by...

Страница 8: ...layed or combined beep test detector X group Y immediate or delayed or combined d 1 Fix the base to the wall using suitable wall plugs and screws i e with a maximum diameter of 3 mm not supplied 2 Pos...

Страница 9: ...2 Unclip the lower lens and rotate it 180 before repositioning it Inside front panel Lower lens Upper lens Detection table for lower lens set at 5 m The lower lens is factory positioned for detection...

Страница 10: ...bay window etc it is advisable to align the detection zone parallel with this surface for improved detection to reduce interference caused by this surface 7 2 Adjusting the detection angle horizontal...

Страница 11: ...n of the fault if dip switch n 4 is ON The options are set using the 6 dip switches inside the detection module 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON Detector in normal user mode factory setting The LED remai...

Страница 12: ...s a deterrence radio transmission depending on parameter setting roughly 3 minutes after the front panel has been masked 7 4 2 Masking detected before Arming When the alarm system is armed and the det...

Страница 13: ...ollowing 4 Check the detection zone using the LED and adjust the detection angle if necessary With each detection the LED indicator lights up once for 2 s the control panel issues the voice message Be...

Страница 14: ...n or Beep armed exit X open 9 Maintenance 9 1 Fault indications 1 Put the control panel in installation mode by asking the user to enter then 2 Open the detector box see 2 Opening the detector 3 Repla...

Страница 15: ...ich this declaration relates are thus compliant with the essential requirements of the following European Directives R TTE Directive 99 5 CE Low Voltage Directive 2006 95 CE ROHS Directive 2002 95 CE...

Страница 16: ...30...

Страница 17: ...31...

Страница 18: ...805220 B 03 2013...

Отзывы: