IOM 1322 • WATER-COOLED SCROLL COMPRESSOR 80 www.DaikinApplied.com
Unit Controller Operation
SET UNIT SPs (11)
Evap Press Sensor
Cir 1 Offset XX.X psi
Cir 2 Offset XX.X psi
The pressure offsets on menus 11 and 12 and the temperature
offsets on menus 10, 11 and 12 correct the controller’s display
of the parameters. The sensors used in these units have a high
degree of repeatability but may need correction (offset). An
accurate pressure gauge or thermometer is used to determine
the correct temperature or pressure. A positive or negative
offset value is then entered to make the controller reading
agree with the measured value.
SET UNIT SPs (12)
Cond Press Sensor
Cir 1 Offset XX.X psi
Cir 2 Offset XX.X psi
SET UNIT SPs (13)
Evap Leaving Water
Temperature Sensor
Offset= 00.0 °F
SET UNIT SPs (13)
LWT Sensors
Evap Offset = 00.0 °F
Cond Offset = 00.0 °F
SET UNIT SPs (14)
OAT/Cond Lvg Water
Temperature Sensor
Offset= 00.0 °F
TGZ Units (Refrig = R134a)
SET UNIT SPs (14)
LWT Sensors
Evap Offset = 00.0 °F
Cond Offset = 00.0 °F
SET UNIT SPs (15)
Suction Temp Sensor
Cir1 Offset 00.0 °F
Cir2 Offset 00.0 °F
WGZ Unit (R410A)
SET UNIT SPs (16)
Clg ResType = X
Clg MaxRes = XX.X ºF
TGZ Unit (Refrig = 134a)
SET UNIT SPs (16)
Liq Line Temp Sensors
Circ1 Offset = 00.0 ºF
Circ2 Offset = 00.0 ºF
WGZ Unit (R410A)
SET UNIT SPs (17)
ENTER PASSWORD: XXXX
Active Password
Level: None
TGZ Unit (Refrig = 134a)
SET UNIT SPs (17)
Clg ResType = X
Clg MaxRes = XX.X ºF
Clg StrtRes = XX.X ºF
TGZ Unit in Cooling Mode
SET UNIT SPs (17)
ENTER PASSWORD: XXXX
Active Password
Level: None
TGZ Unit in Heat Mode
SET UNIT SPs (17)
Htg ResType = X
Htg MaxRes = XX.X ºF
Htg StrtRes = XX.X ºF
TGZ Unit Heat Mode
SET UNIT SPs (18)
ENTER PASSWORD: XXXX
Active Password
Level: None
Two four-digit passwords provide OPERATOR and MANAGER
levels of access to changeable parameters. The passwords
are preprogrammed into the controller. Either password must
be entered using the ENTER PASSWORD (12) screen before
a protected setting can be changed. The operator password is
0100. The manager level is 2001.
Содержание WGZ030DA
Страница 4: ......
Страница 75: ...Unit Controller Operation www DaikinApplied com 75 IOM 1322 WATER COOLED SCROLL COMPRESSOR ...
Страница 76: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Unit Controller Operation ...
Страница 103: ... www DaikinApplied com 103 IOM 1322 WATER COOLED SCROLL COMPRESSOR Maintenance Schedule ...
Страница 104: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 104 www DaikinApplied com Troubleshooting Chart ...
Страница 105: ... www DaikinApplied com 105 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 106: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 106 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 107: ... www DaikinApplied com 107 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 108: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 108 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 109: ... www DaikinApplied com 109 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 110: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 110 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 111: ... www DaikinApplied com 111 IOM 1322 WATER COOLED SCROLL COMPRESSOR Limited Product Warranty ...