www.DaikinApplied.com 51
IOM 1322 • WATER-COOLED SCROLL COMPRESSOR
#
Description
Type
Load
Output OFF
Output ON
5
Motor Control Relay #3 = Compr#3
C1
Starter
Compressor OFF Compressor ON
*6
Condenser Fan #3– Water Cooled =N /Tower Fan
#2-Water Cooled=Y
C1/
UT
Fan Contactor
Fan OFF
Fan ON
*6
Motor Control Relay #5 = Compr#5
(R134a,R410A)
C1
Starter
Compressor OFF Compressor ON
7
Liquid Line #1
C1
Solenoid
Cooling OFF
Cooling ON
8
Condenser Fan #2 – Water Cooled =N /Tower Fan
#1-Water Cooled=Y
C2/
UT
Fan Contactor
Fan OFF
Fan ON
9
Motor Control Relay #2 = Compr#2
C2
Starter
Compressor OFF Compressor ON
10
Motor Control Relay #4 = Compr#4
C2
Starter
Compressor OFF Compressor ON
*11
Condenser Fan #4
C2
Fan Contactor
Fan OFF
Fan ON
*11
Motor Control Relay #6 = Compr#6
(R134a,R410A)
C2
Starter
Compressor OFF Compressor ON
12
Liquid Line #2
C2
Solenoid
Cooling OFF
Cooling ON
13
Condenser Fan #5
C1
Fan Contactor
Fan OFF
Fan ON
14
Hot Gas Bypass #1
C1
Solenoid
Cooling OFF
Cooling ON
15
Hot Gas Bypass #2
C2
Solenoid
Cooling OFF
Cooling ON
*16
Condenser Fan #6
C2
Fan Contactor
Fan OFF
Fan ON
*16
Condenser Fan #4
C2
Fan Contactor
Fan OFF
Fan ON
*17
Condenser Fan #7
C1
Fan Contactor
Fan OFF
Fan ON
*17
Condenser Fan #5&7
(R134a,R410A)
C1
Fan Contactor
Fan OFF
Fan ON
18
Condenser Fan #8
C2
Fan Contactor
Fan OFF
Fan ON
19
Condenser Fan #6&8
C2
Fan Contactor
Fan OFF
Fan ON
Expansion I/O Controller
Digital Outputs
The following parameters are digital outputs from this controller.
Types: C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, UT = Unit
#
Description
Type
Output Off
Output On
1
Evap Water Pump Output #2
UT
Pump Off
Pump On
2
Cond Water Pump Output #2
UT
Pump Off
Pump On
3
Condenser Fan #9
C1
Fan OFF
Fan ON
4
Condenser Fan #10
C2
Fan OFF
Fan ON
Analog Inputs
The following parameters are digital outputs from this controller for Templifier operation only.
Types: C1 = Refrigerant Circuit #1, C2 = Refrigerant Circuit #2, & UT = Unit
#
Description
Type
Output Off
Output On
1
Entering Evaporator Water Temperature
(R134a)
UT
NTC Thermister
(10k@25°C)
-58 to 212°F
2
Demand Limit
(R134a)
UT
4-20 mA Current
0-100 % Load
3
Liquid Line Temperature #1
(R134a)
C1
NTC Thermister
(10k@25°C)
-58 to 212°F
4
Liquid Line Temperature #2
(R134a)
C2
NTC Thermister
(10k@25°C)
-58 to 212°F
Unit Controller Operation
Содержание WGZ030DA
Страница 4: ......
Страница 75: ...Unit Controller Operation www DaikinApplied com 75 IOM 1322 WATER COOLED SCROLL COMPRESSOR ...
Страница 76: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Unit Controller Operation ...
Страница 103: ... www DaikinApplied com 103 IOM 1322 WATER COOLED SCROLL COMPRESSOR Maintenance Schedule ...
Страница 104: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 104 www DaikinApplied com Troubleshooting Chart ...
Страница 105: ... www DaikinApplied com 105 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 106: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 106 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 107: ... www DaikinApplied com 107 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 108: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 108 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 109: ... www DaikinApplied com 109 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 110: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 110 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 111: ... www DaikinApplied com 111 IOM 1322 WATER COOLED SCROLL COMPRESSOR Limited Product Warranty ...