www.DaikinApplied.com 67
IOM 1322 • WATER-COOLED SCROLL COMPRESSOR
Initial Valve Position
When the condenser pump is not in the RUN state, the valve
output will be set as a function of entering condenser water
temperature (ECWT)) per the following graph.
Operation After Start
When the condenser pump is in the RUN state, the valve
output will be controlled in one of two modes as specified by
the Valve/VFD Control set point. The controlled parameter
will be the condenser entering water temperature. When the
desired output signal varies from 0 to 100%, the output voltage
will vary as shown below.
0 to 10 VDC (Valve Type = NC to tower)
10 to 0 VDC (Valve Type = NO to tower)
Valve Set Point Mode
This mode is operational when the Valve/VFD Control set point
is set to Valve Set Point OR Valve SP/VFD Stage. In this mode
the valve output is varied with a proportional-derivative (PD)
algorithm (with dead band) in order to maintain the controlled
parameter (CP) at the desired value. The output is always
limited between the Valve Control Range (Min) set point and
the Valve Control Range (Max) set point. A valve increment
shall be computed once every 5 seconds according to the
following equation.
Increment = [(Error) * (Error Gain set point)] + [(Slope) * (Slope
Gain set point)]
Where: Error = ECWT – Valve Set Point Slope = (Present
CP) – (Previous CP)
When the Error is > the Valve Deadband set point, the valve
position analog output (% of full scale) is updated according to
the following equation.
New %Position = Old %Po Increment/10.
Valve Stage Mode
This mode is only operational when the Valve/VFD Control
set point is set to Valve Stage. In this mode the valve output
is controlled as for Valve Set Point mode (above) except that
the active set point for the controlled parameter is selected
according to the following table.
Number Of Fans ON
Active Set Point
0
Valve Set Point
1
Stage #1 ON
2
Stage #2 ON
Cooling Tower Fan VFD
When the Valve/VFD Control set point is set to None,
Valve Setpoint, OR Valve Stage, this output will be set to 0.
Otherwise, it will be controlled in a manner identical to Valve
Stage Mode (above) except that (1) it will be kept at zero until
the first fan stage is ON and (2) the following set points do not
apply.
Valve Control Range (Min)
Valve Control Range (Max)
Valve Type
Compressor Start/Stop Timing
This section determines when to start or stop a compressor.
There are two separate functions used, one for staging up and
one for staging down.
Stage Up Now
The
Stage Up Now
flag is set based on the following tests:
If Unit mode = Cool AND
no compressors are running AND
LWT error > Start delta + 0.5 * Control Band AND
Motor Protect Timer expired AND
Stage up timer expired THEN
Stage Up Now
= True
If Unit Mode = Cool AND
At least one compressor is running AND
LWT error > 0.5 * Control band AND
Pulldown rate <= Max pulldown rate AND
Compressors running < unit capacity limit AND
Stage up timer expired THEN
Stage Up Now
= True
If Unit mode = Heat AND
no compressors are running AND
LWT error > Start delta + 0.5 * Control Band AND
Motor Protect Timer expired AND
Stage up timer expired THEN
Stage Up Now
= True
If Unit Mode = Heat AND
At least one compressor is running AND
LWT error > 0.5 * Control band AND
Pulldown rate <= Max pulldown rate AND
Compressors running < unit capacity limit AND
Stage up timer expired THEN
Stage Up Now
= True
Unit Controller Operation
Содержание WGZ030DA
Страница 4: ......
Страница 75: ...Unit Controller Operation www DaikinApplied com 75 IOM 1322 WATER COOLED SCROLL COMPRESSOR ...
Страница 76: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Unit Controller Operation ...
Страница 103: ... www DaikinApplied com 103 IOM 1322 WATER COOLED SCROLL COMPRESSOR Maintenance Schedule ...
Страница 104: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 104 www DaikinApplied com Troubleshooting Chart ...
Страница 105: ... www DaikinApplied com 105 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 106: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 106 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 107: ... www DaikinApplied com 107 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 108: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 108 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 109: ... www DaikinApplied com 109 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 110: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 110 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 111: ... www DaikinApplied com 111 IOM 1322 WATER COOLED SCROLL COMPRESSOR Limited Product Warranty ...