IOM 1322 • WATER-COOLED SCROLL COMPRESSOR 70 www.DaikinApplied.com
Network Limit
The maximum unit capacity can be limited by a network signal.
This function is only enabled if the unit control source is set
to network. The maximum unit capacity stage is based on the
network limit value received from the BAS, and is determined
as shown in the following graph.
NOTE:
In order to allow all stages to run, a signal of 100.0%
is required.
Maximum LWT Rate
The maximum rate at which the leaving water temperature
can drop is limited by the Maximum Pull Down Rate set point
when the unit mode is cool. If the rate exceeds this set point,
no more compressors shall be started until the pull down rate
is less than the set point. Running compressors will not be
stopped as a result of exceeding the maximum pull down rate.
Low Ambient Lockout (Water Cooled =
NO Only)
If the OAT drops below the low ambient lockout set point, then
all running circuits will do a normal stop, after the compressors
have stopped the evaporator water pump will stop. Once the
lockout has been triggered, the evaporator water pump will
remain off and no compressors will start until the OAT rises to
the lockout set point plus 5°F.
Manual Compressor Control
The operator can manually enable and disable individual
compressors. When a compressor has been disabled it is
considered unavailable to start in the staging logic. With
Manual Compressor control it is possible to take a damaged
compressor offline while the remaining compressors on the
circuit can still provide some cooling.
A running compressor cannot be disabled until it has been
shutdown. If both of the compressors on a circuit have been
disabled then the circuit is disabled. If both circuits have all of
their compressors disabled, the Unit state will remain “Off”.
Normal Circuit Shutdown
If a condition arises that requires a circuit to shut down, but it
is not an emergency situation, then the circuit will do a pump
down. A normal circuit shutdown will be initiated when any of
the following occur:
• Unit State = Pump Down
•
Circuit Switch = Off
• Low Ambient Lockout
• A normal stage down occurs, and only one compressor
on the circuit is running
• Unit mode = Ice AND the ice set point is reached
Pump Down Procedure
•
If both compressors are running, shut off the appropriate
compressor based on sequencing logic
•
With one compressor left running, turn off hot gas output
and liquid line output
•
Keep running until evaporator pressure reaches the pump
down pressure, then stop compressor
• If evaporator pressure does not reach pump down
pressure within two minutes, stop compressor andrecord
a Failed Pumpdown event in the Event Log.
Liquid Line Solenoid
The liquid line output shall be on any time a compressor on the
circuit is running and the circuit is not performing a pump down.
This output should be off at all other times.
Hot Gas Bypass Solenoid
This output shall be on when one compressor on the circuit
is running and the circuit is not performing a pump down. The
output should be off at all other times including the delay time
described below.
Unit Controller Operation
Содержание WGZ030DA
Страница 4: ......
Страница 75: ...Unit Controller Operation www DaikinApplied com 75 IOM 1322 WATER COOLED SCROLL COMPRESSOR ...
Страница 76: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Unit Controller Operation ...
Страница 103: ... www DaikinApplied com 103 IOM 1322 WATER COOLED SCROLL COMPRESSOR Maintenance Schedule ...
Страница 104: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 104 www DaikinApplied com Troubleshooting Chart ...
Страница 105: ... www DaikinApplied com 105 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 106: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 106 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 107: ... www DaikinApplied com 107 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 108: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 108 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 109: ... www DaikinApplied com 109 IOM 1322 WATER COOLED SCROLL COMPRESSOR Warranty Registration Form Scroll ...
Страница 110: ...IOM 1322 WATER COOLED SCROLL COMPRESSOR 110 www DaikinApplied com Warranty Registration Form Scroll ...
Страница 111: ... www DaikinApplied com 111 IOM 1322 WATER COOLED SCROLL COMPRESSOR Limited Product Warranty ...