Troubleshooting by Indication on the Remote Controller
SiUS30-604
218
Troubleshooting
2.44
“
U8
”
Malfunction of Transmission between Master and
Slave Remote Controllers
Remote
Controller
Display
U8
Applicable
Models
All models of indoor units
Method of
Malfunction
Detection
In case of controlling with 2-remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Decision
Conditions
Normal transmission does not continue for specified period.
Supposed
Causes
Malfunction of transmission between main and sub remote controller
Connection between sub remote controllers
Defect of remote controller PC board
Troubleshooting
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(V2825)
SS1
of both remote controllers is
set to “SUB”.
Set SS1 to “MAIN”; the
power supply off once and
then back on.
Set one remote controller to
“MAIN”; the power supply off
once and then back on.
Turn the power off and then
back on. If a malfunction
occurs, replace the remote
controller PC board.
YES
YES
YES
NO
NO
NO
Using 2-remote
controllers control.
SS1
of remote controller PC boards
is set to “MAIN”.
Содержание VRV - WII
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Страница 13: ...Introduction SiUS30 604 xii...
Страница 27: ...Capacity Range SiUS30 604 14 General Information...
Страница 49: ...Specifications SiUS30 604 36 Specifications...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box...
Страница 273: ...Piping Diagrams SiUS30 604 260 Appendix 1 Piping Diagrams 1 1 Outside Units RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 4D055410...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Страница 277: ...Wiring Diagrams SiUS30 604 264 Appendix 2 Wiring Diagrams 2 1 Outside Unit RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 3D054502A...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Страница 309: ...SiUS39 601 iv Index...