SiUS30-604
Special Operation
Function
77
7.1.2 Oil Return Operation in Heating or Cooling/Heating simultaneous
Operation
[Starting conditions]
Start oil return operation in heating operation referring to the following conditions.
Cumulative compressor operating time after power supply turns on exceeds 2 hours and the time
after the completion of previous oil return operation exceeds 8 hours. And cumulative oil return is
calculated based on Tc, Te compressor load.
Heating & Cooling/heating simultaneous operation oil return
Compressor
—
(M1C)
74 Hz
SVG
(Y4S)
OFF
—
Same as normal
heating operation
Indoor unit control
BS 20RH
20RH
(Y3S)
ON
OFF
OFF
Heating
ON
OFF
ON
BS 20RT
20RT
(Y1S)
OFF
OFF
OFF
Ending condition
2 min.
Max.2 min. Max.4 min.
Max.3 min.
Indoor heating unit
expansion valve
EV
(Y1E)
Normal control
320 pulse
EV1
(Y1E)
20S2=OFF : 2000 pulse
20S2=ON : 180 pulse
Sub-cooling
electronic
expansion valave
EV3
(Y3E)
0 pulse
Main heat
exchanger
electronic
expansion valve
104 Hz
4 way valve 1
20S1
(Y5S)
ON
4 way valve 2
20S2
(Y7S)
Heat exchanger mode
SVP
(Y1S)
ON
SVE
(Y2S)
OFF
SVL
(Y3S)
OFF
EV
(Y1E)
320 pulse
Normal control
Indoor cooling unit
expansion valve
Indoor heating unit
fan
—
(M1, 2F)
OFF
Receiver gas
discharge solenoid
valve
Liquid pipe stop
solenoid valve
(M1, 2F)
Normal control
Indoor cooling unit
fan
SVSL
(Y6S)
ON
2000 pulse
0 pulse
OFF
OFF
ON
OFF
OFF
OFF
ON
Thermostat off :
Thermostat on/Stop :
Indoor unit control
OFF
Hot gas bypass
solenoid valve
Water heat exch.
oil return solenoid
valve
Receiver gas
charging solenoid
valve
Parts name
Preperation
Electrical
symbol
After oil return
operation
During oil return
operation
Symbol
Cooling
Содержание VRV - WII
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Страница 13: ...Introduction SiUS30 604 xii...
Страница 27: ...Capacity Range SiUS30 604 14 General Information...
Страница 49: ...Specifications SiUS30 604 36 Specifications...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box...
Страница 273: ...Piping Diagrams SiUS30 604 260 Appendix 1 Piping Diagrams 1 1 Outside Units RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 4D055410...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Страница 277: ...Wiring Diagrams SiUS30 604 264 Appendix 2 Wiring Diagrams 2 1 Outside Unit RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 3D054502A...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Страница 309: ...SiUS39 601 iv Index...