SiUS30-604
Field Setting
Test Operation
133
3.2.6 Setting of Refrigerant Recovery Mode
When carrying out the refrigerant collection on site, fully open the respective expansion valve of
indoor and outside units
[Operation procedure]
c
In
setting mode 2
with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode” to
ON. The respective expansion valve of indoor and outside units are fully opened. (H2P turns to
display “TEST OPERATION” (blinks), “TEST OPERATION” and “IN CENTRALIZED
CONTROL” are displayed on the remote controller, and the operation is prohibited.
d
Collect the refrigerant using a refrigerant recovery unit. (See the instruction attached to the
refrigerant recovery unit for more detal.)
e
Press Mode button “BS1” once and reset “Setting Mode 2”.
3.2.7 Setting of Vacuuming Mode
In order to perform vacuuming operation at site, fully open the expansion valves of indoor and
outside units to turn on some solenoid valves.
[Operating procedure]
c
With
Setting Mode 2
while the unit stops, set (B) Refrigerant recovery / Vacuuming mode to
ON. The expansion valves of indoor and outside units fully open and some of solenoid valves
open.
(H2P blinks to indicate the test operation, and the remote controller displays “Test Operation”
and “In Centralized control”, thus prohibiting operation.)
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
d
Use the vacuum pump to perform vacuuming operation.
e
Press Mode button “BS1” once and reset “Setting Mode 2”.
Содержание VRV - WII
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Страница 13: ...Introduction SiUS30 604 xii...
Страница 27: ...Capacity Range SiUS30 604 14 General Information...
Страница 49: ...Specifications SiUS30 604 36 Specifications...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box...
Страница 273: ...Piping Diagrams SiUS30 604 260 Appendix 1 Piping Diagrams 1 1 Outside Units RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 4D055410...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Страница 277: ...Wiring Diagrams SiUS30 604 264 Appendix 2 Wiring Diagrams 2 1 Outside Unit RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 3D054502A...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...
Страница 284: ...SiUS30 604 Wiring Diagrams Appendix 271 2 4 BS Unit BSVQ36M 60MVJU 3D045069A...
Страница 289: ...Option List SiUS30 604 276 Appendix 4 Option List 4 1 Optional Accessories Outside Unit 3D055420...
Страница 305: ...Precautions for New Refrigerant R 410A SiUS30 604 292 Precautions for New Refrigerant R 410A...
Страница 309: ...SiUS39 601 iv Index...