SiUS30-604
Test Operation
Test Operation
97
[LED display in the case of multi-outside-unit system] (Same as that in emergency operation)
* Discriminate the operating status of the master unit/slave units through the following LED
display.
Malfunction code
In case of an alarm code displayed on remote controller:
1.1.4 Confirmation on Normal Operation
Conduct normal unit operation after the check operation has been completed.
(1) Confirm that the indoor/outdoor units can be operated normally.
(When an abnormal noise due to liquid compression by the compressor can be heard, stop the
unit immediately, and turn on the crankcase heater to heat up it sufficiently, then start operation
again.)
(2) Operate indoor unit one by one to check that the corresponding outside unit operates.
(3) Confirm that the indoor unit discharges cold air (or warm air).
(4) Operate the air direction control button and flow rate control button to check the function of the
devices.
<Precautions for checking normal operation>
•
For a period of approximately 5 minutes after the compressor stops, even if the ON/OFF
button for the indoor units in one and the same system is pressed, the compressor will
not operate.
•
After stopping the compressor operation using the remote controller, the outside unit
may conduct the residual operation for a period of 5 minutes at maximum.
•
When the check operation is not conducted using the TEST OPERATION button at the
first test operation after installation, the malfunction code “U3” will be displayed. Be sure
to conduct the check operation according to
LED display (
7
:ON
7
7
:OFF
9
9
:Blink)
H1P---H7P H8P
(Factory set)
Master:
Slave 1:
Slave 2:
77
7777777
7777 7
7777777
7777777 9
9
7777777 7
7777777 7
Malfunction code
Installation error
Remedial action
E3
E4
F3
F6
UF
U2
The shutoff valve of an outside unit is left closed.
The cooling water is not provided.
Open the shutoff valve.
Check the operation of cooling water pump etc.
U1
The phases of the power to the outside units are
reversed.
Exchange two of the three phases (L1, L2, L3) to
make a positive phase connection.
U4
No power is supplied to an outside or indoor unit
(including phase interruption).
Check if the power wiring for the outside units are
connected correctly.
(If the power wire is not connected to L2 phase, no
malfunction display will appear and the compressor
will not work.)
UF
Incorrect transmission between units
Check if the refrigerant piping line and the unit
transmission wiring are consistent with each other.
E3
F6
UF
U2
Refrigerant overcharge
Recalculate the required amount of refrigerant from
the piping length and correct the refrigerant charge
level by recovering any excessive refrigerant with a
refrigerant recovery machine.
E4
F3
Insufficient refrigerant
Check if the additional refrigerant charge has been
finished correctly.
Recalculate the required amount of refrigerant
from the piping length and add an adequate
amount of refrigerant.
U7
UF
If an outside unit multi terminal is connected when
there is one outside unit installed
Remove the line from the outside multi terminals (Q1
and Q2).
UF
E4
The operation mode on the remote controller was
changed before the check operation.
Set the operation mode on all indoor unit remote
controllers to “cooling”.
HJ
The heat source water is not circulating.
Make sure that the water pump is running.
1.1.3 Check Operation.
Содержание VRV - WII
Страница 1: ...SiUS30 604 Water Cooled Inverter Series Heat Pump Heat Recovery 60Hz...
Страница 7: ...SiUS30 604 vi Table of Contents Index i Drawings Flow Charts v...
Страница 13: ...Introduction SiUS30 604 xii...
Страница 27: ...Capacity Range SiUS30 604 14 General Information...
Страница 49: ...Specifications SiUS30 604 36 Specifications...
Страница 61: ...Refrigerant Flow for Each Operation Mode SiUS30 604 48 Refrigerant Circuit...
Страница 67: ...SiUS30 604 54 Function 9 8 Heater Control 90 9 9 List of Swing Flap Operations 91 9 10 Freeze Prevention 92...
Страница 271: ...Procedure for Mounting Dismounting of Switch Box SiUS30 604 258 Procedure for Mounting Dismounting of Switch Box...
Страница 273: ...Piping Diagrams SiUS30 604 260 Appendix 1 Piping Diagrams 1 1 Outside Units RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 4D055410...
Страница 276: ...SiUS30 604 Piping Diagrams Appendix 263 1 3 BS Unit BSVQ36MVJU BSVQ60MVJU 4D045338...
Страница 277: ...Wiring Diagrams SiUS30 604 264 Appendix 2 Wiring Diagrams 2 1 Outside Unit RWEYQ60MTJU RWEYQ72MTJU RWEYQ84MTJU 3D054502A...
Страница 279: ...Wiring Diagrams SiUS30 604 266 Appendix RWEYQ60 72 84 144 168 216 252MTJU Operation System Heat Pump 3D055419...
Страница 281: ...Wiring Diagrams SiUS30 604 268 Appendix FXSQ12M 18M 24M 30M 36M 48MVJU FXMQ30M 36M 48MVJU 3D043177A 3D043176A...
Страница 282: ...SiUS30 604 Wiring Diagrams Appendix 269 FXAQ07M 09M 12M 18M 24MVJU FXHQ12M 24M 36M 3D046039C 3D048116...
Страница 283: ...Wiring Diagrams SiUS30 604 270 Appendix FXLQ12M 18M 24MVJU FXNQ12M 18M 24MVJU 3D045644A...