24
|
Troubleshooting
Installer and user reference guide
143
RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
Main code
Sub code
Cause
Solution
Master
Slave 1
Slave 2
Low pressure malfunction:
▪
Stop valve closed
▪
Refrigerant shortage
▪
Indoor unit malfunction
▪
Open stop valves.
▪
Check refrigerant amount
+recharge unit.
▪
Check the user interface's
display
or
transmission
wiring between the outdoor
unit and the indoor unit.
Electronic expansion valve
malfunction (subcool) (Y2E) -
A1P (X21A)
Check connection on PCB or
actuator.
Electronic expansion valve
malfunction (main) (Y1E) - A1P
(X23A)
Check connection on PCB or
actuator.
Electronic expansion valve
malfunction (storage vessel)
(Y3E) - A1P (X22A)
Check connection on PCB or
actuator
Discharge temperature too
high (R21T/R22T):
▪
Stop valve closed
▪
Refrigerant shortage
▪
Open stop valves.
▪
Check refrigerant amount
+recharge unit.
Compressor casing
temperature too high (R8T):
▪
Stop valve closed
▪
Refrigerant shortage
▪
Open stop valves.
▪
Check refrigerant amount
+recharge unit.
▪
Refrigerant overcharge
▪
Stop valve closed
▪
Check refrigerant amount
+recharge unit.
▪
Open stop valves.
Ambient temperature sensor
malfunction (R1T) - A1P
(X18A)
Check connection on PCB or
actuator.