18
|
Piping installation
Installer and user reference guide
75
RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
Example
Description
Example 2.3
a
b
1
2
3
4
5
6
7
8
c
d
e
f
g
h
i
t
u
r
s
H1
H3
H2
Multi outdoor
Branch with refnet header
Example 3
r
s
u
t
With standard multi layout
Indoor unit
Refnet joint
Refnet header
Outdoor multi connection piping kit
Maximum allowable length
▪
Between outdoor and indoor units (single/multi combinations)
Actual piping length
165 m
/135 m
Example 1.1
▪
unit 8: a+b+c+d+e+f+g+p≤165 m
Example 1.2
▪
unit 6: a+b+h≤165 m
▪
unit 8: a+i+k≤165 m
Example 1.3
▪
unit 8: a+i≤165 m
Example 2.1
▪
unit 8: a+b+c+d+e+f+g+p≤135 m
Equivalent length
190 m
/160 m
Total piping length
500 m
/500 m
Example 1.1
▪
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p≤500 m
Example 2.1
▪
a+b+c+d+e+f+g+h+i+j+k+l+m+n+p≤500 m
▪
Between outdoor branch and outdoor unit (only in case of a multi outdoor
installation)
Actual piping length
10 m
Example 3
▪
r, s, t≤10 m; u≤5 m
Equivalent length
13 m