13 Technical data
Installer and user reference guide
60
RXYSQ8~12TMY1B
VRV IV-S system air conditioner
4P404225-1B – 2016.03
13.8
Capacity table: Indoor unit
Total capacity of indoor units needs to be within the specified range.
The connection ratio (CR): 50%≤CR≤130%.
HP class of
outdoor
unit
50%
minimum
CR
(VRV DX)
80%
minimum
CR (RA DX)
100%
nominal CR
130%
maximum
CR
8
100
160
200
260
10
125
200
250
325
12
150
240
300
390
NOTICE
When selecting the total capacity higher than mentioned in
above table, cooling and heating capacity will drop. For
additional information see technical engineering data.