7 Configuration
Installer and user reference guide
31
RXYSQ8~12TMY1B
VRV IV-S system air conditioner
4P404225-1B – 2016.03
#
Action
Button/display
2
Check the status of LED
H6P.
H6P OFF: Unit is currently
not operating under low noise
restrictions.
H6P ON: Unit is currently
operating under low noise
restrictions.
Example: 7‑LEDs display – Mode 1
(in case of RXYSQ8)
You can read out setting [1‑5] (= the total number of connected
indoor units) as follows:
#
Action
Button/display
1
Start from the default
situation.
2
Select mode 1.
BS1 [1×]
3
Select setting 5.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
(= binary 5)
4
Display the value of setting 5.
(there are 8 indoor units
connected)
BS3 [1×]
(= binary 8)
5
Quit mode 1.
BS1 [1×]
Example: 7‑segments display – Mode 1
(in case of 12)
You can read out setting [1‑10] (= the total number of connected
indoor units) as follows:
#
Action
Button/display
1
Start from the default
situation.
2
Select mode 1.
BS1 [1×]
3
Select setting 10.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
4
Display the value of setting
10.
(there are 8 indoor units
connected)
BS3 [1×]
5
Quit mode 1.
BS1 [1×]
7.2.6
To use mode 2
In mode 2 you can make field settings to configure the system. How
to do this differs slightly depending on the model.
Example: 7‑LEDs display – Mode 2
(in case of RXYSQ8)
You can change the value of setting [2‑8] (= T
e
target temperature
during cooling operation) to 4 (= 8°C) as follows:
#
Action
Button/display
1
Start from the default
situation.
2
Select mode 2.
BS1 [5 s]
3
Select setting 8.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
(= binary 8)
4
Select value 4 (= 8°C).
a
: Display the current value.
b
: Change to 4. ("X×"
depends on the current
value, and the value that you
want to select.)
c
: Enter the value in the
system.
d
: Confirm. The system starts
operating according to the
setting.
BS2 [X×]
b
a
BS3 [1×]
c
BS3 [1×]
d
BS3 [1×]
5
Quit mode 2.
BS1 [1×]
Example: 7‑segments display – Mode 2
(in case of 12)
You can change the value of setting [2‑8] (= T
e
target temperature
during cooling operation) to 4 (= 8°C) as follows:
#
Action
Button/display
1
Start from the default
situation.
2
Select mode 2.
BS1 [5 s]
3
Select setting 8.
("X×" depends on the setting
that you want to select.)
BS2 [X×]
4
Select value 4 (= 8°C).
a
: Display the current value.
b
: Change to 4. ("X×"
depends on the current
value, and the value that you
want to select.)
c
: Enter the value in the
system.
d
: Confirm. The system starts
operating according to the
setting.
BS3 [1×]
BS2 [X×]
b
a
BS3 [1×]
c
BS3 [1×]
d
5
Quit mode 2.
BS1 [1×]
7.2.7
Mode 1 (and default situation): Monitoring
settings
In mode 1 (and in default situation) you can read out some
information. What you can read out differs depending on the model.
7‑LEDs display – Default situation (H1P OFF)
(in case of RXYSQ8)
You can read out the following information: