6 Installation
Installer and user reference guide
25
RXYSQ8~12TMY1B
VRV IV-S system air conditioner
4P404225-1B – 2016.03
INFORMATION
The manual refrigerant charge operation will automatically
stop within 30 minutes. If charging is not completed after
30 minutes, perform the additional refrigerant charging
operation again.
INFORMATION
▪ When a malfunction is detected during the procedure
(e.g., in case of closed stop valve), a malfunction code
will be displayed. In that case, refer to
codes when charging refrigerant" on page 25
solve the malfunction accordingly. Resetting the
malfunction can be done by pushing BS3. You can
restart the "Charging" instructions.
▪ Aborting the manual refrigerant charge is possible by
pushing BS3. The unit will stop and return to idle
condition.
10
Open valve A.
11
Charge refrigerant until the remaining determined additional
refrigerant amount is added, and then close valve A.
12
Press BS3 to stop the manual additional refrigerant charge
mode.
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
NOTICE
After adding the refrigerant, do not forget to close the lid of
the refrigerant charging port. The tightening torque for the
lid is 11.5 to 13.9 N•m.
6.7.5
Error codes when charging refrigerant
INFORMATION
If a malfunction occurs:
▪ In case of RXYSQ8: The error code is displayed on the
user interface of the indoor unit.
▪ In case of 12: The error code is displayed
on the outdoor unit's 7‑segments display and on the
user interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm the
malfunction code and take corresponding action,
problems based on error codes" on page 42
.
6.7.6
To fix the fluorinated greenhouse gases
label
1
Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of
a
.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Greenhouse gas emissions
of the total refrigerant charge
expressed as tonnes CO
2
-equivalent
f
GWP = Global warming potential
NOTICE
In Europe, the
greenhouse gas emissions
of the total
refrigerant charge in the system (expressed as tonnes
CO
2
-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
2
Fix the label on the inside of the outdoor unit. There is a
dedicated place for it on the wiring diagram label.
6.8
Connecting the electrical wiring
6.8.1
About connecting the electrical wiring
Typical workflow
Connecting the electrical wiring typically consists of the following
stages:
1
Making sure the power supply system complies with the
electrical specifications of the units.
2
Connecting the electrical wiring to the outdoor unit.
3
Connecting the electrical wiring to the indoor units.
4
Connecting the main power supply.
Field wiring: Overview
Field wiring consists of power supply (always including earth) and
indoor-outdoor communication (= transmission) wiring.
Example:
a
d
b
c
b
g
g
c
f
f
f
h
e
e
e
a
h
h
h
h
h
a
Field power supply (with earth leakage protector)
b
Main switch
c
Earth connection
d
Outdoor unit
e
Indoor unit
f
User interface
g
Power supply wiring (sheathed cable) (230 V)
h
Transmission wiring (sheathed cable) (16 V)
Power supply 3N~ 50 Hz
Power supply 1~ 50 Hz
Earth wiring
Power supply wiring and transmission wiring
It is important to keep the power supply and the transmission wiring
separated from each other. In order to avoid any electrical
interference the distance between both wiring should always be at
least 50 mm.