FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
45
3P432203-7B
10
English
9-2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES
AND WIRE
Power-related
NOTES
1. Shows only in case of protected pipes. Use H07RN-F in
case of no protection.
(Do not lighter than 60245 IEC 57.)
2. Insulated thickness : 1mm or more.
3.
This size is based on IEC 60335-1 (Table 11), and this size
must comply with local codes.
4. If the wiring is in a place where people it can be easily
touched by people, install an earth leakage breaker to
prevent electric shock.
5. When using an earth leakage breaker, make sure to select
one useful also to protection against overcurrent and short-
circuit.
When using an earth leakage breaker only for earth device,
make sure to use a wiring interrupter together.
•
The length of the transmission wiring and remote controller
wiring are as follows.
Length of the transmission wiring and remote controller wiring
9-3 ELECTRICAL CHARACTERISTICS
MCA: Minimum Circuit Amps (A) MFA:Max. Fuse Amps (A)
KW: Fan motor output (kW)
FLA:Full Load Amps (A)
Model
Power supply wiring (including earth wire)
Number
of units
Field
fuses
Wire
Size
20 · 25 · 32 type
1
16A
H05VV-U3G
(NOTE 1)
2.5 mm
2
(NOTE 3)
40 · 50 type
63 type
Model
Transmission wiring
Remote controller wiring
Wire
Size (mm
2
)
20 · 25 · 32 type
Sheathed vinyl cord
or cable (2 wires) (NOTE 2)
0.75 - 1.25
40 · 50 type
63 type
Outdoor unit – Indoor unit
Max. 1000 m
(Total wiring length: 2000 m)
Indoor unit – Remote controller
Max. 500 m
Units
Power supply
Fan motor
Model
Hz Volts Voltage
range
MCA
MFA
KW
FLA
20 · 25 · 32 PDVE
50 220-
240
Min.
198
Max.
264
0.8
16
0.062
0.6
20 · 25 · 32 PDVET
0.7
0.062
0.6
40 NDVE(T)
1.0
0.062
0.8
50 NDVE(T)
1.0
0.13
0.8
63 NDVE(T)
1.1
0.13
0.9
20 · 25 · 32 PDVE
60
220
Min.
198
Max.
242
0.9
16
0.062
0.7
20 · 25 · 32 PDVET
0.8
0.062
0.7
40 NDVE(T)
1.1
0.062
0.9
50 NDVE(T)
1.3
0.13
1.0
63 NDVE(T)
1.4
0.13
1.1
CAUTION
•
Be sure to insulate the duct to prevent condensation from
forming. (Material: glass wool or polyethylene foam, 25 mm
thick)
•
Use electric insulation between the duct and the wall when
using metal ducts to pass metal laths of the net or fence
shape or metal plating into wooden buildings.
•
Be sure to explain about the way of maintaining and cleaning
local procurements (air filter, grille (both air outlet and suction
grille), etc.) to your customer.
9. ELECTRIC WIRING WORK
9-1 GENERAL INSTRUCTIONS
•
Shut off the power before doing any work.
•
All field supplied parts and materials, electric works must
conform to local codes.
•
Use copper wire only.
•
See also the “Wiring Diagram plate” attached to the control
box lid when laying electrical wiring.
•
For details on hooking up the remote controller, refer to the
“REMOTE CONTROLLER INSTALLATION MANUAL”.
•
All wiring must be performed by an authorized electrician.
•
This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B . . . , and be sure the terminal board
wiring to the outdoor unit and BS unit are properly matched. If
wiring and piping between the outdoor unit and an indoor unit
are mismatched, the system may cause a malfunction.
•
A circuit breaker capable of shutting down power supply to
the entire system must be installed.
•
Refer to the installation manual attached to the outdoor unit
for the size of power supply wiring connected to the outdoor
unit, the capacity of the circuit breaker and switch, and wiring
instructions.
•
Be sure to ground the air conditioner.
•
Do not the earth wire should come in contact with gas pipes,
water pipes, lightning rods, or telephone earth wires.
•
Gas pipes: gas leaks can cause explosions and fire.
•
Water pipes: they cannot be grounded if hard vinyl pipes
are used.
•
Telephone earth wire and lightning rods: the ground
potential when struck by lightning gets extremely high.
•
To avoid short circuiting the power supply wire, be sure to use
insulated terminals.
•
Do not turn on the power supply (circuit breaker or earth
leakage breaker) until all other work is done.
Содержание VRV FXDQ-NDVE
Страница 1: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 201710 Engineering Data 50 60 Hz ...
Страница 2: ......
Страница 16: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 14 FXDQ63NDVE with a drain pump 3D045496F Unit mm ...
Страница 17: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 15 FXDQ40NDVET FXDQ50NDVET without a drain pump 3D049701D Unit mm ...
Страница 18: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 16 FXDQ63NDVET without a drain pump 3D049702D Unit mm ...
Страница 26: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 24 FXDQ32PDVE FXDQ32PDVET 3D052157E ...
Страница 27: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 25 9 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET 3D046299G ...
Страница 28: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 26 FXDQ50NDVE FXDQ50NDVET 3D046300G ...
Страница 29: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 27 FXDQ63NDVE FXDQ63NDVET 3D046301G ...
Страница 31: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 29 FXDQ32PDVE FXDQ32PDVET 4D112291 ...
Страница 33: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 31 FXDQ63NDVE FXDQ63NDVET 4D112295 ...
Страница 36: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 34 FXDQ63NDVE FXDQ63NDVET 4D043887Q Unit mm ...
Страница 53: ......
Страница 54: ......
Страница 55: ......