11-3 SETTING THE FILTER SIGN DISPLAY INTERVAL
•
Explain the following to the customer if the filter dirt settings
have been changed.
•
The filter sign display time is set to 2500 hours
(equivalent to 1 year’s use) when shipped.
•
The settings can be changed to not display.
•
When installing the unit in a place with much dusts, set the
filter sign display time to shorter intervals (1,250 hours).
•
Explain it to the customer that the filter needs to be cleaned
regularly to prevent clogging and also the time that is set.
11-4 SETTINGS FOR SEPARATELY SOLD
ACCESSORIES
•
See the instruction manuals included with separately sold
accessories for the necessary settings.
〈
When using a wireless remote controller
〉
•
A wireless remote controller address needs to be set when
using a wireless remote controller. See the installation
manual included with the wireless remote controller for
details on how to make the settings.
Mode No.
FIRST CODE NO.
SECOND
CODE NO.
01
02
10 (20)
0
Filter dirt
low
high
1 (low/high)
Displayed time
(units: hours)
2500/
1250
10000/
5000
3
Filter sign
display
ON
OFF
11. FIELD SETTING AND TEST RUN
〈
Field settings may have to be performed using the
remote controller, depending on the type of installation.
〉
(1) Make sure the control box lids are closed on the indoor
and outdoor units.
(2) Depending on the type of installation, make the field
settings from the remote controller after the power is
turned on, following the “Field Settings” manual which
came with the remote controller.
•
The settings can select “Mode No.”, “FIRST CODE NO.”
and “SECOND CODE NO.”.
•
The “Field Settings” included with the remote controller
lists the order of the settings and method of operation.
•
Lastly, make sure the customer keeps the “Field Settings”
manual, along with the operating manual, in a safe place.
11-1 SETTING THE STATIC PRESSURE SELECTION
•
Select the SECOND CODE NO. for the resistance of the con-
nected duct.
(The SECOND CODE NO. is set to “01” when shipped.)
•
See the technical documentation for details.
11-2 REMOTE CONTROL SETTING
•
Forced off and ON/OFF operation should be selected by
selecting the SECOND CODE NO. as shown in the table
below.
(The SECOND CODE NO. is set to “01” when shipped.)
•
Input A of forced off and ON/OFF operation work as shown in
the table below.
External static
pressure
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Standard
(10Pa)
13(23)
5
01
High static pres-
sure setting
(30Pa)
02
External ON/OFF input
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Forced off
12(22)
1
01
ON/OFF operation
02
n
o
it
a
r
e
p
o
F
F
O
/
N
O
ff
o
d
e
c
r
o
F
Input A “on” to force a stop
(remote controller reception prohibited)
Unit operated by changing input A from
“off” to “on”
Input A “off” to allow remote controller
Unit stopped by changing input A from “on”
to “off”
SETTING
Mode No.
SECOND
CODE NO.
FIELD SET
MODE
FIRST
CODE NO.
11-5
•
If you change the operation mode to “Dry” when VRTsmart
control is in effect, the operation mode is change to “Cooling”
after certain period of time.
If you want to continue dry operation longer, please change
the setting position as mentioned in the table below.
(Setting position of factory setting is “0”.)
Continuous (Not return
to Cooling)
90 min
60 min
10
10
01
02
03
04
30 min
Dry operation
Mode
number
Setting switch
number
Setting position
number
※
If you keep dry operation longer, energy saving
performance decrease.
※
At the time of Group control setting, Dry operation time for the
indoor units in the same group shall be the same setting value.
SWITCHING TIME OF THE DRY OPERATION AT
VRTsmart control SETTING.
NOTE
For VRTsmart control function it is necessary to connect
with an outdoor unit with a compatible function.
Содержание VRV FXDQ-NDVE
Страница 1: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 201710 Engineering Data 50 60 Hz ...
Страница 2: ......
Страница 16: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 14 FXDQ63NDVE with a drain pump 3D045496F Unit mm ...
Страница 17: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 15 FXDQ40NDVET FXDQ50NDVET without a drain pump 3D049701D Unit mm ...
Страница 18: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 16 FXDQ63NDVET without a drain pump 3D049702D Unit mm ...
Страница 26: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 24 FXDQ32PDVE FXDQ32PDVET 3D052157E ...
Страница 27: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 25 9 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET 3D046299G ...
Страница 28: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 26 FXDQ50NDVE FXDQ50NDVET 3D046300G ...
Страница 29: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 27 FXDQ63NDVE FXDQ63NDVET 3D046301G ...
Страница 31: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 29 FXDQ32PDVE FXDQ32PDVET 4D112291 ...
Страница 33: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 31 FXDQ63NDVE FXDQ63NDVET 4D112295 ...
Страница 36: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 34 FXDQ63NDVE FXDQ63NDVET 4D043887Q Unit mm ...
Страница 53: ......
Страница 54: ......
Страница 55: ......