FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

39

3P432203-7B

4

English

(2) Use suspension bolts for installation. Check whether

the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling
before installing the unit.

(Installation pitch is marked on the carton box for installation.
Refer to it to check for points requiring reinforcing.)

4. PREPARATIONS BEFORE INSTALLATION

(1) Confirm the positional relationship between the unit

and suspension bolts. (Refer to Fig. 2)

Install the inspection opening on the control box side where
maintenance and inspection of the control box and drain
pump are easy.  Install the inspection opening also in the
lower part of the unit.

(length: mm)

(2) Make sure the range of the unit’s external static

pressure is not exceeded.

(See the technical documentation for the range of the
external static pressure setting.)

Model

A

B

0

4

7

0

0

7

e

p

y

 2

3

 · 

5

2

 · 

0

2

0

4

9

0

0

9

e

p

y

 

0

5

 

· 

0

4

0

4

1

1

0

0

1

1

e

p

y

 

3

6

B

A

620

500

450×450

(Inspection 

opening size)

Ceiling

620

A

Air outlet

Suspension

bolt pitch

(length : mm)

Air inlet

Control box

(S

uspe

ns

io

bo

lt pi

tc

h )

Allow view 

Inspection door

(Ceiling opening)

Fig. 2

SERVICE SPACE

Drain pump

3. SELECTING INSTALLATION SITE

CAUTION

When moving the unit during or after unpacking, make sure
to lift it by holding its lifting lugs.  Do not exert any pressure on
other parts, especially the refrigerant piping, drain piping and
flange parts.

If you think the humidity inside the ceiling might exceed
30°C and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that
it is no thicker than 10 mm and fits inside the ceiling
opening.

(1) Select an installation site where the following conditions

are fulfilled and that meets with your customer’s approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate can be properly drained.

Where the ceiling is strong enough to bear the indoor unit

weight.

Where the false ceiling is not noticeably on an incline.

Where there is no risk of flammable gas leakage.

Where sufficient clearance for maintenance and service

can be ensured. 

(Refer to Fig. 1)

Where piping between indoor and outdoor units is

possible within the allowable limit. (Refer to the installation

manual for the outdoor unit.)

*H1 dimension means the minimum height of the unit.

Select the *H1, *H2 dimension such that a downward
slope of at least 1/100 is ensured as indicated in

7. DRAIN PIPING WORK

”.

The maintenance space marked with “ * ” is required when
the installation box for adaptor PC board (KRP1BA101) 
sold separately is used.

[ PRECAUTION ]

Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 m away from televisions or 
radios in order to prevent image interference or noise. 
(Depending on the radio waves, a distance of 1 m may not 
be sufficient enough to eliminate the noise.)

If installing the wireless kit in a room with electronic
fluorescent lighting (inverter or rapid start type), the
remote controller’s transmission distance may be
shortened. Indoor units should be installed as far away
from fluorescent lighting as possible.

Control box

Maintenance

space

Maintenance

space

300

or more

*300

or

more

*H2=20 or more

2500 or more

*H1= 240 or more

200

Ceiling

Floor surface

(length : mm)

Fig. 1

Содержание VRV FXDQ-NDVE

Страница 1: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 201710 Engineering Data 50 60 Hz ...

Страница 2: ......

Страница 3: ...teristics 19 7 Safety Devices Setting 20 8 Capacity Tables 21 8 1 Cooling Capacity for Te Auto 21 8 2 Cooling Capacity for Te 6 C 21 8 3 Cooling Capacity for Te 9 C 22 8 4 Heating Capacity 22 9 Fan Performances 23 9 1 FXDQ PDVE T 23 9 2 FXDQ NDVE T 25 10 Sound Levels 28 10 1 FXDQ PDVE T 28 10 2 FXDQ NDVE T 30 11 Centre of Gravity 32 11 1 FXDQ PDVE T 32 11 2 FXDQ NDVE T 33 12 Accessories 35 12 1 Op...

Страница 4: ...2S 63NDV2S 40NDVTS 50NDVTS 63NDVTS FXDQ for Indonesia 20PDVE4 25PDVE4 32PDVE4 20PDVT4 25PDVT4 32PDVT4 40NDVE4 50NDVE4 63NDVE4 40NDVT4 50NDVT4 63NDVT4 Note FXDQ has following 2 series as shown below FXDQ PDVE NDVE PDV2S NDV2S PDVE4 NDVE4 with a Drain Pump FXDQ PDVET NDVET PDVTS NDVTS PDVT4 NDVT4 without a Drain Pump VE 1 phase 220 240 220 V 50 60 Hz VET 1 phase 220 240 220 V 50 60 Hz V2S 1 phase 22...

Страница 5: ...dB A 28 26 23 28 26 23 Sound power level HH H L dB A 56 54 51 56 54 51 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duc...

Страница 6: ...ermal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air filter Drawing No Specifications C 3D109082B Sound level C 4D112291 Notes 1 Indoor temp 27 CDB 19 CWB outdoor temp 35 CDB Equivalent piping len...

Страница 7: ...28 26 23 Sound power level HH H L dB A 56 54 51 56 54 51 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air ...

Страница 8: ...Thermal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air filter Drawing No Specifications C 3D109082B Sound level C 4D112291 Notes 1 Indoor temp 27 CDB 19 CWB outdoor temp 35 CDB Equivalent piping l...

Страница 9: ... 30 28 26 33 30 27 Sound power level HH H L dB A 58 56 54 61 58 55 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duct fl...

Страница 10: ... Thermal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air filter Drawing No Specifications C 3D109082B Sound level C 4D112295 Notes 1 Indoor temp 27 CDB 19 CWB outdoor temp 35 CDB Equivalent piping ...

Страница 11: ... 26 33 30 27 Sound power level HH H L dB A 58 56 54 61 58 55 Safety devices Fuse Thermal protector for fan motor Fuse Thermal protector for fan motor Refrigerant control Electronic expansion valve Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges ...

Страница 12: ...se Thermal protector for fan motor Refrigerant control Electronic expansion valve Standard accessories Operation manual Installation manual Drain hose Sealing pads Clamps Washers Insulation for fitting Clamp metal Washer fixing plate Screws for duct flanges Air filter Drawing No Specifications C 3D109082B Sound level C 4D112295 Notes 1 Indoor temp 27 CDB 19 CWB outdoor temp 35 CDB Equivalent pipin...

Страница 13: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 11 3 Dimensions 3 1 FXDQ PDVE T FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE with a drain pump 3D049799D Unit mm ...

Страница 14: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 12 FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET without a drain pump 3D050732C Unit mm ...

Страница 15: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 13 3 2 FXDQ NDVE T FXDQ40NDVE FXDQ50NDVE with a drain pump 3D045494E Unit mm ...

Страница 16: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 14 FXDQ63NDVE with a drain pump 3D045496F Unit mm ...

Страница 17: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 15 FXDQ40NDVET FXDQ50NDVET without a drain pump 3D049701D Unit mm ...

Страница 18: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 16 FXDQ63NDVET without a drain pump 3D049702D Unit mm ...

Страница 19: ...Q63NDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET Refrigerant pipe connection port diameters Unit mm Model Gas Liquid FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET φ12 7 φ6 4 FXDQ63NDVE FXDQ63NDVET φ15 9 φ9 5 4D104913 ...

Страница 20: ...XDQ PDVE T FXDQ NDVE T EDFMT391749 18 5 Wiring Diagrams FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET 3D103337 ...

Страница 21: ...PDVE T FXDQ NDVE T EDFMT391749 19 6 Electric Characteristics FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET 3D112184 ...

Страница 22: ...V 5 A 250 V 5 A Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Drain pump thermal fuse C Model FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE Printed circuit board fuse 250 V 5 A 250 V 5 A 250 V 5 A Fan motor thermal protector C OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 OFF 130 5 ON 83 15 Drain pump thermal fuse C 145 145 145 Model FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET Printed ...

Страница 23: ...ping length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 2 Cooling Capacity for Te 6 C Model Capacity indication Indoor air temp 14 CWB 16 CWB 18 CWB 19 CWB 20 CWB 22 CWB 24 CWB 20 CDB 23 CDB 26 CDB 27 CDB 28 CDB 30 CDB 32 CDB TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC FXDQ20PDVE FXDQ20PDVET 20 1 5 1 4 1 8 1 6 2 1 1 8...

Страница 24: ...Notes 1 These capacity tables are for use when selecting a VRV indoor unit The actual capacity of the VRV system depends on factors such as the selected model of outdoor units outdoor air temperature and piping length Please confirm that the corrected capacity of the VRV system satisfies the required heat load 2 shows rated condition 8 4 Heating Capacity Model Capacity indication Indoor air temp 1...

Страница 25: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 23 9 Fan Performances 9 1 FXDQ PDVE T FXDQ20PDVE FXDQ25PDVE FXDQ20PDVET FXDQ25PDVET 3D052156E ...

Страница 26: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 24 FXDQ32PDVE FXDQ32PDVET 3D052157E ...

Страница 27: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 25 9 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET 3D046299G ...

Страница 28: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 26 FXDQ50NDVE FXDQ50NDVET 3D046300G ...

Страница 29: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 27 FXDQ63NDVE FXDQ63NDVET 3D046301G ...

Страница 30: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 28 10 Sound Levels 10 1 FXDQ PDVE T FXDQ20PDVE FXDQ20PDVET FXDQ25PDVE FXDQ25PDVET 4D112287 4D112290 ...

Страница 31: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 29 FXDQ32PDVE FXDQ32PDVET 4D112291 ...

Страница 32: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 30 10 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET FXDQ50NDVE FXDQ50NDVET 4D112292 4D112294 ...

Страница 33: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 31 FXDQ63NDVE FXDQ63NDVET 4D112295 ...

Страница 34: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 32 11 Centre of Gravity 11 1 FXDQ PDVE T FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET 4D049300M Unit mm ...

Страница 35: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 33 11 2 FXDQ NDVE T FXDQ40NDVE FXDQ50NDVE FXDQ40NDVET FXDQ50NDVET 4D043886R Unit mm ...

Страница 36: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 34 FXDQ63NDVE FXDQ63NDVET 4D043887Q Unit mm ...

Страница 37: ... BRC1C62 Note 4 Navigation remote controller Wired remote controller BRC1E62 Note 4 Simplified remote controller BRC2C51 Remote controller for hotel use BRC3A61 Adaptor for wiring KRP1B56 Wiring adaptor for electrical appendices 1 KRP2A53 Wiring adaptor for electrical appendices 2 KRP4A54 Remote sensor KRCS01 1B Installation box for adaptor printed circuit board KRP1BA101 Note 2 3 External control...

Страница 38: ...nstall the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work in consideration of strong winds typhoons or earthquakes Improper installation may result in an accident suc...

Страница 39: ...leted Do not discard them 1 Decide upon a line of transport 2 Leave the unit inside its packaging while moving until reaching the installation site Where unpacking is unavoidable use a sling of soft material or protective plates together with a rope when lifting to avoid damage or scratches to the unit When moving the unit at or after opening hold the unit by the hanger brackets Do not apply force...

Страница 40: ... your customer Did you hand the operation manual and warranty over to your customer Did you explain about the way of maintaining and cleaning local procurements air filter grille both air outlet and suction grille etc to your customer Did you hand manuals of local procurements in case equipped over to your customer The items with WARNING and CAUTION marks in the operation manual are the items pert...

Страница 41: ...se glass wool or polyethylene foam as insulation so that it is no thicker than 10 mm and fits inside the ceiling opening 1 Select an installation site where the following conditions are fulfilled and that meets with your customer s approval Where optimum air distribution can be ensured Where nothing blocks air passage Where condensate can be properly drained Where the ceiling is strong enough to b...

Страница 42: ... Open the installation hole Pre set ceilings Once the installation hole is opened in the ceiling where the unit is to be installed pass refrigerant piping drain piping transmission wiring and remote controller wiring It is not necessary if using a wireless remote controller to the unit s piping and wiring holes See 6 REFRIGERANT PIPING WORK 7 DRAIN PIPING WORK and 10 WIRING EXAMPLE After opening t...

Страница 43: ...op of the flare nut connection Main unit 4 Tighten the upper nut 6 REFRIGERANT PIPING WORK For the outdoor unit refrigerant piping refer to the installation manual attached to the outdoor unit Carry out insulation of both gas and liquid refrigerant piping securely If not insulated it may cause water leakage For gas piping use insulation material of which heat resistant temperature is not less than...

Страница 44: ... any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation or burns if touched When brazing the refrigerant piping perform nitrogen replacement first or perform the brazing CAUTION 2 while feeding nitrogen into the refrigerant piping CAUTION 1 and finally connect the indoor unit using the flare connections Refer to Fig 9 CAUTION 1 When brazing ...

Страница 45: ...Inspection window Portable pump Inspection lid Refrigerant pipes Bucket Service drain hole Drain outlet with rubber cap Indoor PC board ASSY Terminal block Terminal block Remote controller terminal connection method Power supply Single phase 50 Hz 220 V 240V Single phase 60Hz 220 V Power terminal connection method PRECAUTIONS FOR DRAIN RAISING PIPE Make sure the drain raising pipe height is no hig...

Страница 46: ...omething similar to prevent air escaping Class 20 25 32 40 50 63 Number of positions 16 22 26 Portable pump Refrigerant pipes Bucket Air outlet Drain outlet Connection screw 7 accessory Field supply Field supply Field supply Field supply Flange Flange Aluminum tape Aluminum tape Main unit Insulation material Air inlet side Air outlet side 1 Install the drain piping Make sure the drain works proper...

Страница 47: ... to insulate the duct to prevent condensation from forming Material glass wool or polyethylene foam 25 mm thick Use electric insulation between the duct and the wall when using metal ducts to pass metal laths of the net or fence shape or metal plating into wooden buildings Be sure to explain about the way of maintaining and cleaning local procurements air filter grille both air outlet and suction ...

Страница 48: ...10 as shown in the Fig 17 to prevent outside pres sure being exerted on the wiring connections and clamp firmly Be sure to attach power supply wiring and earth wire to the control box with the clamp When doing the wiring make sure the wiring is neat and does not cause the control box lid to stick up then close the cover firmly When attaching the control box lid make sure you do not pinch any wires...

Страница 49: ...als with insulation sleeve or insulate the wirings properly Connect the terminal as shown in Fig 20 Do not carry out soldering finish when stranded wires are used Otherwise the loosening of wires may result in abnormal heat radiation Abnormal heating may occur if the wirings are not tightened securely Use the required wirings connect them securely and fix these wirings securely so that external fo...

Страница 50: ... unit 2 Max No of indoor units Crossover wire P1 P2 Remote controller 1 MAIN Remote controller 2 SUB Input A 1 P 2 P 1 F 2 F 1 T 2 T FORCED OFF REMOTE CONTRL TRANSMISSION WIRING No 3 system When including BS unit 10 2 CONTROL BY 2 REMOTE CONTROLLERS Controlling 1 indoor unit by 2 remote controllers When using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER 1 I...

Страница 51: ...e sure the customer keeps the Field Settings manual along with the operating manual in a safe place 11 1 SETTING THE STATIC PRESSURE SELECTION Select the SECOND CODE NO for the resistance of the con nected duct The SECOND CODE NO is set to 01 when shipped See the technical documentation for details 11 2 REMOTE CONTROL SETTING Forced off and ON OFF operation should be selected by selecting the SECO...

Страница 52: ... wiring was done incorrectly or that the power is not on so check again CAUTION Always stop the test run using the remote controller to stop operation 4 After finishing the test run make sure to check drainage in the drain pump according to 7 DRAIN PIPING WORK Remote control display Content display There is a short circuit at the FORCED OFF terminals T1 T2 display The test run has not been perform...

Страница 53: ......

Страница 54: ......

Страница 55: ......

Страница 56: ...parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage electrical shock fire or explosion Read the user s manual carefully before using this product The user s manual provides important s...

Отзывы: