FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
43
3P432203-7B
8
English
1.
Remove the control box lid. Connect the remote controller
and power supply (single-phase, 50 Hz 220-240 V or
single-phase, 60Hz 220V) respectively to the terminal block
and securely connect the earth also (as shown in the figure
below).
CAUTION
Securely clamp the cables with the clamps (9)(10) offered
as accessories as shown in Fig. 17 so that tension will not
be applied on the cable connection areas.
2.
Confirm that the control box lid is closed before turning on
the power.
3.
Remove the inspection lid.
4.
Gradually pour approximately 1L of water from the
inspection window into the drain pan to check drainage.
CAUTION
Be sure to prevent an external force from being exerted on
the float switch.
(This may cause breakage.)
5.
Attach the inspection lid.
6.
Perform the following operation using the remote controller,
and check drainage.
•
Select the inspection/test operation button “
” using
the remote controller. The unit will engage the test
operation. Press the operation selector button “
”, and
select FAN OPERATION “
”.
•
Press the ON/OFF button “
”. (The indoor fan and
drain pump will operate.)
CAUTION
The fan will turn also at the same time. Take due care.
Do not touch the drain pump to prevent electric shock.
7.
Make sure to use the remote controller in finishing the
operation.
CAUTION
•
The connection opening on the drain piping may vary
depending on the model, so check the model name and use
the right method for that model.
•
Make sure all water is out before making the duct connection.
In case of PDVET, NDVET type (without drain pump)
TEST
TRANSMISSION
WIRING
REMOTE
CNTRL
T1
F1
FORCED
OFF
P2
F2
P1
T2
TRANSMISSION
WIRING
REMOTE
CNTRL
T1
F1
FORCED
OFF
P2
F2
P1
T2
L
N
N
L
L
N
Inspection window
Portable pump
Inspection lid
Refrigerant pipes
Bucket
Service drain hole
Drain outlet
(with rubber cap)
Indoor PC board
(ASSY)
Terminal block
Terminal block
Remote controller
terminal connection
method
Power supply:
Single phase,
50 Hz, 220 V~
240V
Single phase,
60Hz, 220 V
Power terminal
connection
method
〈
PRECAUTIONS FOR DRAIN RAISING PIPE
〉
•
Make sure the drain raising pipe height is no higher than
600 mm.
•
Place the drain raising pipe vertically and make sure it is no
further than 300 mm from the unit.
(Refer to Fig. 13)
〈
PRECAUTIONS
〉
Drain piping connections
•
Do not connect the drain piping directly to sewage pipes that
smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain piping and corrode the heat
exchanger.
•
Do not twist or bend the drain hose (2), so that excessive
force is not applied to it.
(This type of treatment may cause leaking.)
•
If you are using central drain piping, follow the procedure
outlined in the figure 10.
•
Select central drain piping of proper size according to the
capacity of the connected unit.
(2) After piping work is finished, check drainage flows
smoothly, with manner described below.
CAUTION
•
The electric wiring work shall be performed by qualified
electricians.
•
If workers not having the electrician qualification have
performed the electric wiring work, the steps 3 to 7 shall be
performed after the
TEST RUN
.
Metal clamp (1)
Drain hose (2)
Tape
2
1
.
g
i
F
1
1
.
g
i
F
(accessory)
(accessory)
≤
4 mm
Large sealing
pad (5)
Metal clamp (1)
(accessory)
(accessory)
Drain raising pipe
Metal clamp (1) (accessory)
Drain hose (2) (accessory)
Ceiling slab
300 mm or less
Hanging bracket
Adjustable range
(600mm or less)
(Field supply)
1 – 1.5m
Fig. 13
Drain hose (2) (accessory)
Horizontal or
upward slope
If there is an air bank, noise may be generated
as a result of a water backflow when the drain
pump comes to a stop.
Locate the drain hose horizontally
or with a little upward gradient.
Содержание VRV FXDQ-NDVE
Страница 1: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 201710 Engineering Data 50 60 Hz ...
Страница 2: ......
Страница 16: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 14 FXDQ63NDVE with a drain pump 3D045496F Unit mm ...
Страница 17: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 15 FXDQ40NDVET FXDQ50NDVET without a drain pump 3D049701D Unit mm ...
Страница 18: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 16 FXDQ63NDVET without a drain pump 3D049702D Unit mm ...
Страница 26: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 24 FXDQ32PDVE FXDQ32PDVET 3D052157E ...
Страница 27: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 25 9 2 FXDQ NDVE T FXDQ40NDVE FXDQ40NDVET 3D046299G ...
Страница 28: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 26 FXDQ50NDVE FXDQ50NDVET 3D046300G ...
Страница 29: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 27 FXDQ63NDVE FXDQ63NDVET 3D046301G ...
Страница 31: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 29 FXDQ32PDVE FXDQ32PDVET 4D112291 ...
Страница 33: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 31 FXDQ63NDVE FXDQ63NDVET 4D112295 ...
Страница 36: ...FXDQ PDVE T FXDQ NDVE T EDFMT391749 34 FXDQ63NDVE FXDQ63NDVET 4D043887Q Unit mm ...
Страница 53: ......
Страница 54: ......
Страница 55: ......