Electrical installation
Installer and user reference guide
119
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
NOTICE
Precautions when making knockout holes:
▪
Avoid damaging the casing and underlying piping.
▪
After making the knockout holes, we recommend to remove the burrs and paint
the edges and areas around the edges using repair paint to prevent rusting.
▪
When passing electrical wiring through the knockout holes, wrap the wiring with
protective tape to prevent damage.
a
b
c
d
a
Knockout hole
b
Burr
c
Remove burrs
d
If there are any possibilities that small animals enter the system through the
knockout holes, close the holes with packing materials (to be prepared on-site)
20.1.4 About electrical compliance
This equipment complies with:
▪
EN/IEC 61000‑3‑11
provided that the system impedance Z
sys
is less than or equal
to Z
max
at the interface point between the user's supply and the public system.
-
EN/IEC 61000‑3‑11 = European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated current ≤75 A.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a system impedance Z
sys
less
than or equal to Z
max
.
▪
EN/IEC 61000‑3‑12
provided that the short-circuit power S
sc
is greater than or
equal to the minimum S
sc
value at the interface point between the user's supply
and the public system.
-
EN/IEC 61000‑3‑12 = European/International Technical Standard setting the
limits for harmonic currents produced by equipment connected to public low-
voltage systems with input current >16 A and ≤75 A per phase.
-
It is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if necessary, that the
equipment is connected ONLY to a supply with a short-circuit power S
sc
greater
than or equal to the minimum S
sc
value.
Single outdoor unit
Model
Z
max
[Ω]
Minimum S
sc
value [kVA]
REMA5
—
2598
REYA8
—
2789
REYA10
—
3810
REYA12
—
4157
REYA14
—
4676
REYA16
—
5369