21
|
Configuration
Installer and user reference guide
141
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
[2‑60]
Supervisor remote controller setting. A power reset is required to save this setting.
For details about the supervisor remote controller, see
60] or refer to the remote controller installation and user
reference guide.
[2‑60]
Description
0 (default)
No supervisor remote controller connected to the
system
1
Supervisor remote controller connected to system
[2‑65]
Automatic leak detection interval time.
This setting is used in conjunction with setting [2‑88].
[2‑65]
Time between automatic leak detection executions
[days]
0 (default)
365
1
180
2
90
3
60
4
30
5
7
6
1
[2‑81]
Cooling comfort setting.
This setting is used in conjunction with setting [2‑8].
[2‑81]
Cooling comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful
For more information and advice about the impact of these settings, see
"21.2 Energy saving and optimum operation"
[2‑82]
Heating comfort setting.
This setting is used in conjunction with setting [2‑9].
[2‑82]
Heating comfort setting
0
Eco
1 (default)
Mild
2
Quick
3
Powerful