Charging refrigerant
Installer and user reference guide
109
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
Inch piping
Metric piping
Piping
Weight factor
Piping
Weight factor
Ø19.1 mm
0.23
Ø19 mm
0.22
Connection ratio requirements.
When selecting indoor units, the connection ratio
must comply with the following requirements. For more information, see the
technical engineering data.
Other combinations than those mentioned in the table are not allowed.
Indoor units
Maximum
(a)
Total CR
(b)
CR per type
(c)
Type
CR
VRV DX
64
50~130%
VRV DX
50~130%
(a)
Maximum number allowed excluding BS units and EKEXV kits
(b)
Total CR = Total indoor unit capacity connection ratio
(c)
CR per type = Allowable capacity connection ratio per indoor unit type