21
|
Configuration
Installer and user reference guide
137
REMA5+REYA8~20A7Y1B
VRV 5 heat recovery
4P687640-1 – 2022.07
▪
For details concerning the charging procedure, see
▪
For details concerning the calculation of additional refrigerant charge amount,
see
"19.4 To determine the additional refrigerant amount"
107].
▪
For guidance concerning the input of the additional refrigerant charge amount
and leak detection function see
"21.3 Using the leak detection function"
147].
[2‑18]
Fan high static pressure setting.
In order to increase the static pressure the outdoor unit fan is delivering, this
setting should be activated. For details about this setting, see technical
specifications.
[2‑18]
Description
0 (default)
Deactivated.
1
Activated.
[2‑20]
Manual additional refrigerant charge/BS/indoor unit connection check
[2‑20]
Description
0 (default)
Manual additional refrigerant charge deactivated.
1
Manual additional refrigerant charge activated.
To stop the manual additional refrigerant charge
operation (when the required additional refrigerant
amount is charged), push BS3. If this function was not
aborted by pushing BS3, the unit will stop its operation
after 30 minutes. If 30 minutes was not sufficient to add
the needed refrigerant amount, the function can be
reactivated by changing the field setting again.
2
Perform a BS/indoor unit connection check.
Perform a BS units and indoor units connection check
where for each indoor unit is checked if the piping and
communication wiring are connected to the same
branch pipe port.
[2‑21]
Refrigerant recovery/vacuuming mode.
In order to achieve a free pathway to reclaim refrigerant out of the system or to
remove residual substances or to vacuum the system it is necessary to apply a
setting which will open required valves in the refrigerant circuit so the reclaim of
refrigerant or vacuuming process can be done properly.
[2‑21]
Description
0 (default)
Deactivated.
1
Activated.
To stop the refrigerant recovery/vacuuming mode, push
BS3. If BS3 is not pushed, the system will remain in
refrigerant recovery/vacuuming mode.