IM 915-13 • VISION - EXTENDED SIZES 30 www.DaikinApplied.com
Daikin Applied Fan Array
Table 15: DDPL Factors for Free and Ducted Inlet –
Non-Standard Density Method, Daikin Applied Piezo Ring
DDPL Size
C1 Free Inlet
C1 Ducted Inlet
12
783.66
792.43
15
767.48
763.62
16
732.77
757.40
18
612.29
619.65
20
653.83
652.65
22
674.42
673.16
24
679.53
681.34
27
656.57
660.15
30
691.07
692.12
33
675.26
677.89
36
675.83
676.67
40
699.51
694.22
44
681.07
681.01
Table 16: DDPL Factors for Free and Ducted Inlet –
Standard Density Method, Daikin Applied Piezo Ring
DDPL Size
Free Inlet F
Ducted
Inlet F
Area A
Wheel
Diameter
12
1004.66
1016.46
0.344
12.40
15
1261.99
1260.20
0.439
14.00
16
1526.96
1572.35
0.552
15.75
18
1675.69
1672.77
0.721
18.25
20
2117.33
2110.61
0.865
20.00
22
2710.75
2693.35
1.074
22.25
24
3312.67
3319.41
1.300
24.50
27
3901.60
3929.94
1.582
27.00
30
5017.64
5033.71
1.957
30.00
33
5942.72
5979.46
2.362
33.00
36
7274.52
7316.07
2.885
36.50
40
9179.91
9089.14
3.513
40.25
44
10891.71
10880.24
4.285
44.50
Optional Transducer for Piezometer Rings
A transducer is available for Piezometer rings. Factory
mounting locations for the fan transducer is shown in
for direct-drive plenum fans.
for fan array. Wiring for the transducer is field-supplied and
installed.
Содержание Vision