IM 915-13 • VISION - EXTENDED SIZES 52 www.DaikinApplied.com
Equipment Warranty Registration Form
AHU Equipment Warranty Registration Form (continued)
13F-4153 (07/18)
5
Select Yes or No. If not applicable to the type of unit, select N/A.
VIII. Design Flow calibration
A. Verify power is supplied to the MicroTech III unit controller . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
No
N/A
B. Verify that the shipping screws have been removed from the measuring station vane . . . . . . . . . . . . Yes
No
N/A
C. Examine station for damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
No
N/A
D. Record Level Position after calibration
• LH Level Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________
• RH Level Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ____________
NOTE: This is viewed in the MicroTech III controller, in the Min OA setup menu.
IX. GAS BURNER CHECK, TEST, & START
Specifications:
For gas, see Forced Draft Gas Burner Installation and Maintenance Bulletin. (IM 684 and IM 685)
A. Gas Furnace:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Model no. __________________
B. Gas Burner: . . . . . . . . . . . . . . . . . . . . . . . . . . .Model no.___________________ Serial no. ___________________
C.
Gas Type firing:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Single Stage ________ Modulation ________
D.
Gas Rated firing rate (MBH input):
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ._________________
E. Gas Altitude (ft. above sea level): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ._________________
F. Is there a circulating tank? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
No
N/A
G. Input (CFH): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
H. Gas pressure at burner (inches w.c.): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
I. CO
2
(%) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
J. CO
2
(%): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
K.
Pilot flame only in microamps (steady at low fire):
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
L. Pilot Tap-gas pressure (inches w.c.): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
M. Motor only/burner FLA running amps: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
N. High limit control OK? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Yes
No
N/A
O. Flame safeguard (microamps): . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________
P.
Flame failure shutoff (seconds):
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _________________