Daikin Applied EC Fan Array
www.DaikinApplied.com 37
IM 915-13 • VISION - EXTENDED SIZES
Optional Piezometer Point Airflow
Measurement Device
A Piezometer point is an option with EC fans to measure
airflow through the fan. The device consists of a piezometer
point mounted in the throat of the funnel and a static pressure
tap mounted near the inlet of the funnel. The pressure drop is
measured from the tap located near the inlet of the funnel to
the piezometer point in the throat. The inlet tap is connected
to the high-pressure side of the transducer and the piezometer
point is connected to the low-pressure side.
A transducer is always factory supplied when the Piezometer
Option is selected with an EC Fan.
shows the
installation for EC fans.
See the equations and factors required to calculate flow using
the piezometer point:
Non-Standard Density Method
The following equation is used to measure the flow for
non-standard density:
ACFM = C1 × A × √(ΔP/ρ)
where: A = Inlet funnel throat area (square feet) - from
ΔP = The differential in static pressure from the piezometer ring
and the inlet pressure tap (inches w.g.)
ρ = Air density (pounds mass/cubic foot)
C1 = Value from
Standard Density Method
The equation can be simplified by assuming standard density
and assuming funnel dimensions match the drawing dimensions.
shows the factor (F) for each fan size and type. The
equation then becomes the following:
For standard air (ρ = 0.075 lb/ft3):
ACFM = F × √ (ΔP)
ΔP = The differential in static pressure from the piezometer ring
and the front pressure tap (inches w.g.)
Table 17: ECM Factors for Free and Ducted Inlet —
Non-Standard Density Method
ECM Size
C1 Free Inlet
C1 Ducted Inlet
355
774.47
774.47
450
783.31
783.31
560
658.54
658.54
630
666.68
666.68
355D
802.05
802.05
450D
783.31
783.31
Table 18: ECM Factors for Free and Ducted Inlet —
Standard Density Method
ECM Size
Free Inlet F
Ducted Inlet F
Area A
355
774.47
774.47
0.485
450
783.31
783.31
0.778
560
658.54
658.54
1.341
630
666.68
666.68
1.667
355D
1459.58
1459.58
0.498
450D
2283.43
2283.43
0.798
Figure 65: Piezometer Transducer
Содержание Vision