P
erforManCe
Fan Performance for PSC Motor (Sizes 009 - 036)
Table 19: PSC motor CFM values
Unit Size
Rated
Airflow
Speed
External Static Pressure (in-H
2
O) [Dry Coil and STD Filter) (inches of water column)
0 .00
0 .05
0 .10
0 .15
0 .20
0 .25
0 .30
0 .35
0 .40
009
300
High
430
390
350
320
280
-
-
-
-
Low
400
360
330
290
250
-
-
-
-
012
400
High
430
390
350
320
-
-
-
-
-
Low
400
360
330
-
-
-
-
-
-
015
500
High
700
700
690
670
660
640
620
590
570
Low
600
600
590
580
570
550
530
510
480
018
600
High
700
700
690
670
660
640
620
590
570
Low
600
600
590
580
570
550
530
510
480
021
700
High
880
820
780
750
720
690
650
600
520
Low
740
710
690
680
650
610
580
540
-
024
800
High
880
820
780
750
720
690
650
600
-
Low
740
710
690
680
650
610
-
-
-
030
1000
High
1,380
1,360
1,340
1,310
1,280
1,250
1,210
1,170
1,130
Low
1,150
1,140
1,130
1,110
1,090
1,070
1,040
1,000
960
036
1200
High
1,380
1,360
1,340
1,310
1,280
1,250
1,210
1,170
1,130
Low
1,150
1,140
1,130
1,110
1,090
1,070
1,040
1,000
960
Note:
Add 0.01" ESP for the optional discharge diffuser, and 0.02" ESP for the optional return air grille.
IM 986-11 • Vertical Stack WSHP 44 www.DaikinApplied.com
Содержание VHF
Страница 2: ......
Страница 61: ...Notes Comments Form WS CTS 00 01 Rev 4 14 IM 986 11 Vertical Stack WSHP 61 www DaikinApplied com...
Страница 62: ...IM 986 11 Vertical Stack WSHP 62 www DaikinApplied com...
Страница 63: ......