P
erforManCe
Fan Performance for Constant CFM EC Motor (Sizes 015 - 036)
Table 21: Single stage units with constant CFM EC motor
Unit
Size
MicroTech III Unit Controller
3
I/O Expansion Module
2
Setting
Maximum
ESP
(in . WC .)
1
Low CFM
Heat
1
High CFM
Heat
1
Low CFM
Cool
1
High CFM
Cool
Setting
Fan Only
Hydronic
Heat
015
4 (High)
0 .40
500
540
500
540
A
500
500
3 (Standard)
440
500
440
500
B
440
440
2 (Medium)
390
440
390
440
C
390
390
1 (Low)
390
390
390
390
D
290
290
018
4 (High)
0 .40
600
680
600
680
A
600
600
3 (Standard)
530
600
530
600
B
530
530
2 (Medium)
470
530
470
530
C
470
470
1 (Low)
470
470
470
470
D
360
360
021
4 (High)
0 .40
700
770
700
770
A
700
700
3 (Standard)
610
700
610
700
B
610
610
2 (Medium)
530
610
530
610
C
530
530
1 (Low)
530
530
530
530
D
400
400
024
4 (High)
0 .40
800
900
800
900
A
800
800
3 (Standard)
700
800
700
800
B
700
700
2 (Medium)
600
700
600
700
C
600
600
1 (Low)
600
600
600
600
D
450
450
030
4 (High)
0 .40
1000
1120
1000
1120
A
1000
1000
3 (Standard)
880
1000
880
1000
B
880
880
2 (Medium)
760
880
760
880
C
760
760
1 (Low)
760
760
760
760
D
580
580
036
4 (High)
0 .40
1200
1310
1200
1310
A
1200
1200
3 (Standard)
1050
1200
1050
1200
B
1050
1050
2 (Medium)
910
1050
910
1050
C
910
910
1 (Low)
910
910
910
910
D
710
710
Notes:
1
The unit is capable of high-low fan performance through the use of a 2-stage thermostat wired to specific terminals for High-Low CFM.
2
Units are shipped at setting 3 (standard). Fan speed settings may be changed via the 4-position fan speed
selector switch located inside the control box.
3
Refer
to
Figure 56 on page 47
for location of jumpers JP1 and JP2 on the I/O expansion module. Refer to
Table 23 on page 47
for jumper configurations.
IM 986-11 • Vertical Stack WSHP 46 www.DaikinApplied.com