erforManCe
Performance For Constant Torque EC Motor (Sizes 009 & 012)
Table 22: Fan settings and performance
Unit Size
I/O Expansion Module
Setting
External Static Pressure (inches of water column)
0
0 .05
0 .1
0 .15
0 .2
0 .25
0 .3
0 .35
0 .4
009
A
430
410
390
370
350
340
320
300
280
B
420
400
380
360
340
320
300
270
250
C
350
330
310
290
270
250
230
210
190
D
370
340
310
280
250
220
190
160
130
012
A
450
430
410
390
370
340
320
300
280
B
420
400
380
360
340
310
290
270
250
C
400
370
350
330
310
290
260
240
220
D
360
330
300
270
240
210
180
150
120
Table 23: I/O expansion module jumper configuration
Setting
I/O Expansion Module Configuration
JP1
JP2
A
Open
Open
B
Shorted
Open
C
Open
Shorted
D
Shorted
Shorted
Note:
Refer to
Figure 56
for location of jumpers JP1 and JP2 on the I/O expansion module.
Figure 56: JP1 & JP2 location on the I/O expansion module
JP1
JP2
www.DaikinApplied.com 47
Vertical Stack WSHP • IM 986-11