17
Foundation bolts position
UHA075/100B5
Installation
Working condition
Installation dimensios and environment limits
Item
Description
Power supply voltage
Rated voltage ±10%
Power supply frequency Rated frequency ±1%
Variations between phases Rated voltage ±2%
Air quality
Must not contain solute that can corrode copper, aluminum or iron.
Flow rate of chilled water
0.5 - 2.0m/s
Pressure of chilled water
< 1.0Mpa
Quality of water
"Must not contain solute that can corrode copper, iron, or welding material.
For details on the water quality requirements, see Water Quality Management."
Installation site
Take anti-snow and ventilation measures as required.
Ambient temp.
Refer to the Performae Data.
Relative humidity
<90%
Note:
1. The unit is strictly tested before delivery and can work safely in the rated working conditions.
2. For the performance of the unit in different working conditions, please refer to performenc data.
3. This is the normal operating temperature range for the unit. Beyond this temperature range, the unit
can only operate for a short moment before a failure alarm is triggered.
Units must be installed by DAIKIN service staff or by specially trained personnel.
Units must installed by following relevant national and local electric, building and environment protection
standards as well as the installation manual.
50
0
445
900
>490
900
900
445
>1390×(N-1)+1790
≥
300
840
≥
150
≥
114
0
≥
150
Foundation bolt M12x200