■  All-day hot water supply
   Service capacity of the water tank V

water tank

 (the total capacity under the higher water level is the service 

capacity):

G

j

 is the producing water volume of the unit under worst local conditions

■  Timing hot water supply system
   Service capacity of the water tank V

water tank

 (the total capacity under the higher water level is the service 

capacity):

Gjis the producing water volume of the unit under worst local conditions

Thermal insulation must be applied for the water tank which should meet the following conditions: 
1.  Ensure that the temperature difference of the water tank in a day and night should be not more than 5ºC.
2.   The design of thermal insulation structure should ensure good thermal insulation effect, convenient 

construction, be fire-proofing, water-proofing, durable and beautiful. 

3.   Dismountable thermal insulations structure should be adopted at the access hole of the water tank. 
4.   Water tanks placed outdoors should be configured with protective layer which should have functions of 

thermal insulation layer protection and water proofing. Metal protective layer is recommended, such as 

galvanized steel sheet at 0.3~0.8mm thickness or enclosure made of anti-rust aluminum sheet. Prevent 

rain water from entering at the joint of the shell by overlap joint technology.

Note: recommend the water tank capacity should be no less than 5 times of the water volume of the 

ordinary type of unit; For northern area with cold weather, the capacity of the water tank should be 

no less than the designed daily water consumption in principle. 

According to the project's needs, a set of auxiliary electric heater can be installed as backup system 

which will be started up during equipment maintenance period when a temporary failure occurs for the 

equipment. Besides, the backup system can also make up capacity degradation of the unit when the ambient 

temperature is extremely low so as to guarantee producing water volume of the unit.
Usually, the capacity of the auxiliary electric heater will be: W=a*Q

2

=a* (Q-Q

1

). (Where, a is the margin 

coefficient with the value range of 1.0~1.5; the value of a should be higher in northern area; it may be 1.5 in 

cold northern areas).
For area with outdoor ambient temperature in winter lower than -7ºC, it is recommended to configure auxiliary 

heating equipment with heating capacity equivalent to the unit to ensure hot water supply when the heat 

pump unit does not run. Cost for hot water production can be significantly reduced by hot water production by 

heat pump water heater in summer and transition season, which has even better economic performance for 

boiler reconstruction projects in northern areas.

Formula (8)

Formula (9)

Water tank selection calculation

Selection of auxiliary electric heater (Backup)

24

(

1

.

1

h

water tank

K

G

G

V

j

r

(        )

24

(

1

.

1

h

water tank

K

G

G

V

j

r

(         )

Содержание UHA075B5

Страница 1: ...eat Pump Water Heater Modular Air Source Heat Pump Water Heater Catalogue Engineering Data Model UHA075 100 200B5 Refrigerant R410A Heating Capacity 30 40 80kW ED UHA B5 V01 ODP 0 R410A ODP 0 R410A DA...

Страница 2: ...oving machinery and electrical power hazard may cause severe personal injury or death Disconnect and lock off power before servicing equipment Model Series 2 Nomenclature 2 Features 3 Specifications 5...

Страница 3: ...Combination Qty UHA075B5 30 kW 16 UHA100B5 40 kW 16 UHA200B5 80 kW 16 Product code UHA Air source heat pump water heater DAIKIN brand Heating capacity code 075 100 200 Design series A B C Refrigerant...

Страница 4: ...quid refrigerant is sprayed into the middle of the scroll compressor cooling chamber to cool down effectively and reduce the exhaust gas temperature so as to ensure the reliability and security By adv...

Страница 5: ...ifferent units and can be combined freely between different models to meet hot water needs of different places When design capacity of the units change or phased investment of project is required it c...

Страница 6: ...rer without prior notice Model UHA075B5 UHA100B5 UHA200B5 Nominal capacity kW 30 40 80 Nominal producing water l h 645 860 1720 Nominal power input kW 6 83 8 71 18 22 COP W W 4 39 4 59 4 39 Nominal cu...

Страница 7: ...m2 1 99 2 56 3 86 Condenser fan Type Drive Low noise axial fan Low noise axial fan Low noise axial fan Qty 1 1 2 Blade model ASG30 ASG30 ASG30 Motor poles 10 8 8 Air volume m3 8725 11846 23692 Compre...

Страница 8: ...B5 UHA200B5 Compressor Rated running current A 19 24 24 Locked rotor AMP LRA A 98 142 142 IP Insulation grade IPX4 IPX4 IPX4 Unit operating current A 13 2 17 3 33 4 Unit max running current A 21 3 27...

Страница 9: ...0 Hot water return Rc1 1 2 Hot water outlet Rc1 1 2 14 20 Foundation bolt 840 1249 1515 4 Foundation bolt 4 14 20 UHA200B5 19 844 19 45 815 270 815 45 1990 880 1780 267 1513 179 247 824 840 20 14 Hot...

Страница 10: ...Operating range Performance Data Operating range 10 15 20 25 30 35 40 45 50 55 15 10 5 0 5 10 15 20 25 30 35 40 45 Ambient temperature Water tank temperature Water tank temperature Ambient temperatur...

Страница 11: ...72 6 80 6 57 6 33 6 40 30 Heating capacity kW 18 92 24 21 29 78 32 39 34 99 37 55 40 10 40 44 40 77 43 79 Heating power kW 7 56 7 60 7 75 7 81 7 87 7 94 8 00 7 74 7 47 7 59 40 Heating capacity kW 17 9...

Страница 12: ...49 8 57 8 61 8 66 8 71 8 72 8 72 8 55 8 37 8 45 COP 2 64 3 35 3 81 4 00 4 30 4 59 4 88 5 17 5 45 5 73 5 98 Water production m3 h 0 47 0 61 0 70 0 74 0 80 0 86 0 92 0 97 1 00 1 03 1 09 UHA200B5 Heatin...

Страница 13: ...m3 h DMHA200B5 140 120 100 80 60 40 20 0 0 2 6 8 10 12 14 16 18 20 4 Note Unit water pressure drop is measured at unit water inlet and water outlet UHA200B5 UHA100B5 DMHA100B5 DMHA200B5 0 0 1 2 3 4 5...

Страница 14: ...13 Wiring Diagrams UHA075 100BM5 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6...

Страница 15: ...14 UHA075 100BS5 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6...

Страница 16: ...15 UHA200BM5 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6...

Страница 17: ...16 UHA200BS5 1 4 5 3 2 7 8 6 1 4 5 3 2 7 8 6...

Страница 18: ...and ventilation measures as required Ambient temp Refer to the Performae Data Relative humidity 90 Note 1 The unit is strictly tested before delivery and can work safely in the rated working conditio...

Страница 19: ...A075 100B5 must be fixed by 4 M12x220 bolts UHA200B5 must be fixed by 8 M12x220 bolts 5 6 rubber cushions of 20mm thick must be installed between the unit and the groundwork 6 N represents the number...

Страница 20: ...h the heat sinks of the heat exchanger bare handedly as they might cut your fingers 4 Dispose all plastic bags properly and keep them away from children Space allotted for an array of units Hoisting t...

Страница 21: ...breakdown even incur bodily injuries Screw down the unit using anchor bolts so that it will not fall off in case of strong wind or earthquakes To avoid damages caused by strong wind or earthquakes The...

Страница 22: ...and Drainage Calculate all day hot water consumption amount based on the set water temperature of the storage tank Gr all day hot water consumption amount m3 t rated hot water temperature C t 60 C in...

Страница 23: ...etween the unit and the auxiliary heat source as well as the economic performance should be considered for unit selection If the unit is selected based on working conditions in summer large auxiliary...

Страница 24: ...ecommend the water tank capacity should be no less than 5 times of the water volume of the ordinary type of unit For northern area with cold weather the capacity of the water tank should be no less th...

Страница 25: ...ter flow rate Selection of hot water circulation booster pump at the user side Head of the hot water circulation booster pump at the user side H3 should be 1 1 1 2 times of the sum of the height diffe...

Страница 26: ...70 130 separate toile Bed day 110 200 Medical staff Person shift Out patient department clinic Patient time 70 130 8 Housing part of the convalescent hospital and the nursing home Bed day 100 160 24 6...

Страница 27: ...0 120 35 Shower kindergarten 30 180 35 Shower nursery 15 90 35 Nozzle of the washbasin 15 25 30 Rinsing sink pool 180 50 5 Hospital convalescent hospital nursing home Hand wash basin 15 25 35 Rinsing...

Страница 28: ...la Therefore supposing that the length of pipeline at a certain diameter is L the fractional head loss of the section of pipeline will be P IL Work out fractional head loss of various sections of pipe...

Страница 29: ...erified on this basis Besides pipe diameter can then be selected in more scientific and reasonable way to achieve overall economy and rationality Diameter of the steel tube mm Closed water system Open...

Страница 30: ...on construction is recommended for the equipment straight pipeline and fitting where service is not required dismountable insulation construction is recommended for valves flange and other places wher...

Страница 31: ...ump Softened water must meet the following requirements Besides water should be meet the standard of domestic water Water quality requirements Item Benchmark value Tendencies Corrosion Scaling Benchma...

Страница 32: ...r should not be lower than the nominal value of the unit Configure circulating water pump with appropriate flow rate and pressure head at the circulating water side Water supply safety valve must be i...

Страница 33: ...n as below Hydraulic system installation schematic diagram For single unit F SV6 F Gate valve Check valve Thermometer Soft connector Water pump Water flow switch Y shaped filter Water pressure gauge C...

Страница 34: ...or a group of combined units Notes 1 Before putting into normal use for the first time be sure to operate circulating water pumps for a certain period of time clean the filter and ensure that there is...

Страница 35: ...nd should be connected into the electrical cabinet Refer to Water level switch and overflow prevention switch connection for details 5 Low water level switch must be installed above the water outlet t...

Страница 36: ...ater system installation correctness 1 The pipeline is firmly connected without water leakage sound thermal insulation anti corrosion or anti rusting measures for the pipeline 2 Complete valves conven...

Страница 37: ...troller operation 2 Wire controller setting 1 Check water tank temperature setting 50 C by default Set value may be modified in commissioning process Reset to default values after commissioning 2 Star...

Страница 38: ...water filter in the water system periodically Replenishing refrigerant and lubricant Each unit is filled with enough refrigerant and lubricant before delivery If the system operates smoothly customers...

Страница 39: ...hether wires are securely connected Whether the working current is abnormal fluctuation 10 Discharge air temperature of the compressor Check the oil level Check the color of the lubricant 2 Controller...

Страница 40: ...er they are customer provided The connecting ports are only for control signal but not for driving the parts and it s for master unit wiring only slave unit doesn t need to wire 2 SV6 is solenoid valv...

Страница 41: ...pc Apc Bin Ain Bpc Apc Bin Ain Master 0 Slave 13 Slave 14 Slave Wired controller Power adapter A conductor WTC pair with cross section area of at least 0 5mm2 or 20AWG B insulator C Screen layer twist...

Страница 42: ...of auto re start after power on SW1 4 ON remote start stop OFF no remote start stop SW1 5 ON with water system auxiliary heating OFF without water system auxiliary heating Note Address numbers must b...

Страница 43: ...cate the status of the unit ON OFF Timed ON OFF a timing schedule can be set for a maximum of 7 days with up to 4 timed actions each day Real time clock Error code display speeds up diagnosis Blue bac...

Страница 44: ...Single Not defrost No display Single Defrosting DEFROST 1 Dual Not defrost No display Dual System 1 defrosting DEFROST 1 Dual System 2 defrosting DEFROST 2 Dual two system defrosting DEFROST 12 Singl...

Страница 45: ...ter The parameter name blinks You can press the or key to set the parameter value and then press Enter to save the setting result 3 You can repeat step 2 to set other parameters note password access w...

Страница 46: ...ay Timing of one week can be set cyclically till timing setting exits 9 To cancel a timing set the time of this timing to 00 00 10 To cancel all timed actions press and hold Mode Unit until you hear a...

Страница 47: ...H5 temperature sensor malfunction 9 22 Dicharge superheat of 1 is too low 32 45 TH6 temperature sensor malfunction 10 23 Dicharge superheat of 2 is too low 33 46 TH7 temperature sensor malfunction 11...

Страница 48: ...ion ER18 Overload of pump ER33 Discharge temperature 1 is too high ER48 TH9 temperature sensor malfunction ER19 Lack of water flow ER34 Suction temperature 2 is too high ER49 TH10 temperature sensor m...

Страница 49: ...ller 7 Failure of communication ports on the control panel of the master unit Replace 8 Failure of communication ports on the wired controller Replace 9 Incorrect address setting for the master unit C...

Страница 50: ...is configured correctly by referring to the electric circuit 2 Check whether the resistor of the malfunctioned compressor meets specification requirements 2 Over current of the fan 2 the overload pro...

Страница 51: ...indicator of the unit displays ER23 and the wired controller displays 23 Dicharge superheat of 2 is too low 1 The low pressure sensor or temperature sensor has broken down Replace 2 EXV control unrea...

Страница 52: ...D indicator of the unit displays ER33 and the wired controller displays 33 Discharge temperature 1 is too high 1 The electronic expansion valve is not opened as expected Check and troubleshoot the ele...

Страница 53: ...0 TH1 temperature sensor malfunction TH1 temperature sensor is not properly plugged or has broken off Check the control module and replug the temperature sensor TH1 temperature sensor is shorted open...

Страница 54: ...temperature sensor is not properly plugged or has broken off Check the control module and replug the temperature sensor TH6 temperature sensor is shorted open Test whether the resistance of TH6 senso...

Страница 55: ...not properly plugged or has broken off Check the control module and replug the temperature sensor TH11 temperature sensor is shorted open Test whether the resistance of TH11 sensor meets specification...

Страница 56: ...e too high low 1 Entering leaving water temperature too high See item 41 2 water tank temperature too low Heating heater or unit heating 3 TH5 sensor malfunction Replace sensor 40 The LED indicator of...

Страница 57: ...accessories can result in water or refrigerant leakage electrical shock fire or explosion Read the User s Manual carefully before using this product The User s Manual provides important safety instruc...