49
S/N
Error code
Symptom
Possible cause
Solution
3
The LED indicator of the unit
displays ER16 and the wired
controller displays 16
Overload of compressor or
fan in #1
1. Over current of the
compressor #1, the overload
protector triggered.
1. Check whether the
electric current parameter
of the overload protector
is configured correctly by
referring to the electric circuit.
2. Check whether the
resistor of the malfunctioned
compressor meets
specification requirements.
2. Over current of the fan
#1, the overload protector
triggered.
1. Check whether the
electric current parameter
of the overload protector
is configured correctly by
referring to the electric circuit.
2. Check whether the
resistor of the malfunctioned
fan meets specification
requirements.
4
The LED indicator of the unit
displays ER17 and the wired
controller displays 17
Overload of compressor or
fan in #2
1. Over current of the
compressor #2, the overload
protector triggered.
1. Check whether the
electric current parameter
of the overload protector
is configured correctly by
referring to the electric circuit.
2. Check whether the
resistor of the malfunctioned
compressor meets
specification requirements.
2. Over current of the fan
#2, the overload protector
triggered.
1. Check whether the
electric current parameter
of the overload protector
is configured correctly by
referring to the electric circuit.
2. Check whether the
resistor of the malfunctioned
fan meets specification
requirements.
5
The LED indicator of the unit
displays ER18 and the wired
controller displays 18
Overload of pump
Over current in the pump
has triggered the overload
protector.
1. Check whether the electric
current parameter of the
overload pump is configured
correctly by referring to the
electric circuit.
2. Check whether the
resistor of the malfunctioned
pump meets specification
requirements.
6
The LED indicator of the unit
displays ER19 and the wired
controller displays 19
Lack of water flow
1. Pump is too small
Replace the pump
2. Blocked of water filter
Clean water filter
3. Air inside water system
Discharge air by opening the
pump
4. Water pressure drop to
large, water system is not
balance
Optimize the water system
5. Blocked of other parts in
water system
Check and repair