In addition to the parameters listed in the table, the abbreviations in the graph are:
-
Pevap = evaporating pressure;
-
As% = opening signal percentage for external/exhaust air.
In normal operating conditions the signal controlling the external air and exhaust air dampers can range from the min.
setpoint stored in parameter “DA12” to the max. setpoint in parameter “DA13” (opening of the recirculated air damper is
complementary).
If the evaporating pressure increases and reaches the setpoint stored in parameter “DA30”, the value of the damper ope
-
ning signal is limited.
Within differential “DA31” the signal is linearly limited between the min. and max. setpoint values stored in parameters
“DA38” and “DA39” respectively.
After limiting the damper opening value, the signal is fixed at the value set in parameter “DA39” for the entire differential
stored in parameter “DA41”, if the evaporating pressure drops below the setpoint in parameter “DA30”.
The damper opening signal starts following the ongoing opening percentage again only after evaporating pressure values
drop below the difference “DA30” – “DA41”.
3.14.3 Limitation based on evaporating pressure in heating mode
When a refrigerant circuit in the unit is operating in heating mode, the evaporating pressure may limit the damper control
signal.
The parameters concerned are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
DA12
30
%
External air - FC / FH - Min opening
DA13
100
%
External air - FC / FH - Max opening
DA30
7.00
bar
External air - Opening limitation - Winter oper. - Min evap. press. threshold for activa
-
tion
DA31
2.00
bar
External air - Opening limitation - Winter oper. - Min evap. press. diff. for activation
DA38
0
%
External air - Opening limitation - Min opening for evap. press.
DA39
60
%
External air - Opening limitation - Max opening for evap. press.
DA41
2.00
bar
External air - Opening limitation - Deactivation diff. for cond. press.
A graphical representation is shown below.
DA34
DA39
DA13
DA12
%
Pevap (bar)
DA38
DA41
DA35
Fig. 33 Damper command in free cooling mode
3 Software functions
Содержание UATYA-B
Страница 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Страница 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 126: ...ESIE21 02 2021 03 Copyright 2021 Daikin...