117
Service manual
Daikin R32 Rooftops UATYA-B
ESIE21-02 – 2021.03
4.6.4 Air quality probes
Air quality: CO
2
and VOC
Alarm code
AL74 for Co
2
probe; AL75 for VOC probe
Reason for activation
When the value measured by the analogue input is outside the set operating range
Reset
When the value measured by the analogue input falls within the set operating range
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Air change
Air change is not allowed if it is dependant on the value of a malfunctioning probe.
The other devices
They follow their control
4 Alarms