4.2.4 Return temperature alarm
The controller always checks that the return air temperature values are within the required operating range.
The parameters involved are shown in the table.
The values of the parameters are representative. In specific cases, different values can be set.
Parameter Value UM
Description
PAL82
35.0
°C
Return air - High temperature threshold
PAL83
5.0
°C
Return air - High temperature differential
PAL84
15.0
°C
Return air - Low temperature threshold
PAL85
5.0
°C
Return air - Low temperature differential
PAL86
60
-
Return air - Max. number of alarms per hour
High return air temperature alarm
Alarm code
AL28
Reason for activation
When the temperature value measured by the probe on the return line is greater than the
setpoint in parameter “PAL82”
Reset
When the temperature value measured by the probe on the return line is lower than the
difference between “PAL82” and “PAL83”
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL86”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
They follow their control
Low return air temperature alarm
Alarm code
AL29
Reason for activation
When the temperature value measured by the probe on the return line is lower than the
setpoint in parameter “PAL84”
Reset
When the temperature value measured by the probe on the return line is greater than the
difference between “PAL84” and “PAL85”
Reset mode
Automatic; switches to manual after the trip occurrences per hour set in “PAL86”
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
All devices
They follow their control
Limitation of air temperature in return line active
Alarm code
AL26
Reason for activation
When the temperature value measured by the probe on the return line is lower than the
setpoint in parameter “ST21”.
Reset
When the temperature value measured by the probe on the return line is greater than the
sum of “ST21” + “ST22”.
Reset mode
Automatic
Alarm icon
Flashing
AlarmLog
Yes
Alarm relay
Based on “alarm.conf” file
Devices
Behaviour in the event of an alarm
Dehumidification demand
It follows the function designed to limit the air temperature in the return line.
4 Alarms
Содержание UATYA-B
Страница 1: ...Operation manual Daikin R32 Rooftops UATYA B ESIE21 02...
Страница 4: ...4 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 122: ...122 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 123: ...123 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 124: ...124 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 125: ...125 Service manual Daikin R32 Rooftops UATYA B ESIE21 02 2021 03 Page intentionally blank...
Страница 126: ...ESIE21 02 2021 03 Copyright 2021 Daikin...